This article gives an introduction to IEEE 485 method for the selection and calculation of battery capacity.
The selection of the physical [[batteries|battery]] (cells) is dependant on several factors:
The Ah or Ampere-hour capacity is the current a battery can provide over a specified period of time. For example 100Ah @ C10 rate to end of discharge of 1.75 V/cell means the battery can provide 10 Amps for 10 hours to an end of discharge voltage of 1.75 V per cell.
Different battery manufacturers will use different Cxx rates depending on the market or application at which their batteries are targeted. Typical rates used are C3, C5, C8, C10 and C20. Because of this it is important, when comparing batteries from different manufacturers.
Ah is used for sizing batteries based on constant [[electric current|current]] methods and watts/cell on constant [[Electrical Power|power]] methods.
This standard details methods for defining the dc loads and for sizing a lead-acid battery to supply those loads in full float operation. A brief description of the method presented by the standard follow. For a full and accurate description, refer to the full standard.
Loads are classified as:
| Continuous | Non-continuous | Momentary |
|---|---|---|
| Lighting Continuous Motors | Emergency motors Fire protection systems | Switchgear operations Valve operations ( < 1 min) |
Note: commonly momentary loads are assumed to last for 1 minute during battery sizing calculations.
The standard recommends a duty cycle be drawn showing the anticipated loads (in [[Ampere]] or power) for the required duration of battery backup time.
IEEE 485 Std. Recommended Practice for Sizing Lead Acid Batteries for Stationary Applications - Typical Duty Cycle
Considerations
Number of Cells and Cell Voltage - the number of cells is estimated based on the maximum battery voltage and float charge voltage:
The minimum battery voltage is the minimum system voltage (including voltage drops across cables). Given the minimum cell voltage the minimum cell voltage is given by:
Temperature Correction - at temperature decreases the capacity of a cell decreases (and vise verse as the temperature increases). Manufacturers quote cell capacity at a given temperature and appropriate correction factors should be used for other temperatures.
Aging Factor - battery performance is relatively stable through out its life, dropping of rapidly towards the end. To ensure the battery can meet the design requirements throughout its life the standard suggestions the initial capacity should be 125% of the design capacity.
Design Margin - to cater for unexpected circumstances (increased loads, poor maintenance, recent discharge, etc.) it is common to allow a design margin of 10% to 15%.
Sizing Methodology - the required capacity of the cell FS is given by:
Where S can be any integer from 1 to N depending on the section being calculated and FS is expressed in watt-hours or ampere-hours depending on which Ct is used.
The required uncorrected cell size F, is then given by:
where:
There are two ways of expressing capacity:
Term Rt
The term Rt is the number of amperes each plate can supply for t minutes, at 25oC to a defined minimum cell voltage.
giving:
Term Kt
The term Kt is the ratio of ampere-hour capacity, at a standard time rate, at 25oC and to a defined minimum voltage which can be delivered for t minutes.
giving:
Rt is not equal to 1/Kt because each factor is expressed in different units.