Understanding Circuit Breaker Markings 

By on

schneiderNSXNamePlate
Typical Circuit Breaker Nameplate
IEC 60947 is the circuit breaker standard and covers the marking of breakers in detail.  Any manufacturer following this standard should comply with the markings.

Name Plate and Breaker Markings

The illustration shows a standard nameplate from a Schneider NSX circuit breaker.   Other manufacturers should have similar information on the breaker.  The standard requires the following by information to be identified and marked on the circuit breaker.

Visible and legible when breaker installed:

  • rated current (In)
  • suitability for isolation, if applicable
  • indication of the open and closed positions

Marked, but need not be visible when installed:

  • manufacturer's name or trade mark and circuit breaker type designation or serial number
  • manufacturing standards the breaker complies with
  • utilization category
  • rated operational voltage (Ue)
  • rated impulse withstand voltage (Uimp)
  • rated frequency and/or the indication d.c.
  • rated service short-circuit breaking capacity (Ics) at corresponding rated voltage (Ue)
  • rated ultimate short-circuit breaking capacity (Icu) at corresponding rated voltage (Ue)
  • rated short-time withstand current (Icw), and associated short-time delay (for utilization category B)
  • line and load terminals (unless their connection is immaterial)
  • neutral pole terminal, if applicable ( by the letter N)
  • protective earth terminal, where applicable, by symbol
  • reference temperature for non-compensated thermal releases, if different from 30 °C

Additional Circuit Breaker Information

In addition to the above the following should be either marked on the circuit breaker or made available in technical documentation:

  • rated short-circuit making capacity (Icm)
  • rated insulation voltage (Ui),
  • pollution degree if other than 3
  • conventional enclosed thermal current (Ithe) if different from the rated current
  • IP Code, where applicable
  • minimum enclosure size and ventilation data (if any) to which marked ratings apply
  • details of minimum distance between circuit-breaker and earthed metal parts for circuit breakers intended for use without enclosures
  • suitability for environment A or environment B, as applicable
  • r.m.s. sensing, if applicable

Auxiliary Devices

Any auxiliary devices should be marked or technical information provided with the following:

  • rated control circuit voltage and frequency of any closing
  • rated control circuit voltage and frequency of any shunt release and/or under-voltage release
  • rated current of indirect over-current releases
  • number and type of auxiliary contacts and rated frequency
  • rated voltages of auxiliary switches (if different from those of the main circuit)

Symbols

The standard identifies the following symbols in connection with circuit breaker markings:

IEC60947Symbols

 

  Hopefully now, the next time we look at a break it should all make sense.



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus



Smarter Electrical Distribution

The other day I came across an article in Technology Review on the development of a smart transformer. A professor at North Carolina State University is...

What happened to the cable notes?

If you are wondering what happened to our cable notes, the short answer is that we have moved them to myCableEngineering.com.  The "Knowledge Base" at...

Copyright Infringement

myElectrical does not support or promote the use of copyrighted material without the copyright owner's consent. If you believe that material for which...

Understanding LV Circuit Breaker Fault Ratings

I think this post is going to be helpful to several of our readers. While the IEC low voltage circuit breaker Standard [IEC 60947-2, Low voltage switchgear...

Harmonised Cable Codes and Colours

Within Europe the European Committee for Electrotechnical Standardization (CENELEC) has standardised the both the designation and colour of cables.   ...

Generator Sizing & Operation Limits

When selecting a generator, there are inherent limits on the active and reactive power which can be delivered. Generators are normally sized for a certain...

How to Check a Circuit is Dead

If you want to check a circuit is dead (not live), you should always use the three point method. First check a known live circuit, then check the dead...

Generation of a Sine Wave

A fundamental concept behind the operation of alternating current systems is that voltage and current waveforms will be sinusoidal – a Sine Wave. This...

Batteries

A battery consists of one or more cells, each of which use stored chemical energy to produce electrical energy, There are many types of cells and these...

How to measure power supply quality

If your are ever called out to troubleshoot something on your electrical system, one of the first things consider is the supply voltage. You want to ensure...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note