Low Voltage Fault Tables 

By on

The following tables provide quick order of magnitude fault levels for a a range of typical low voltage situations.

Transformer LV Terminal Fault Levels (230/400 V)

Short circuit current, Isc (kA) at the LV terminals of a 3-phase HV/LV transformer.

Transformer rated power (kVA) 50 100 160 250 315 400 500 630 800 1000 1250 1600 2000 2500
Transformer rated (LV) current (A) 69 137 220 344 433 550 687 866 1100 1375 1718 2199 2749 3437
oil-immersed Psc = 250MVA 1.17 33.1 3.40 5.41 8.38 10.5 13.2 16.4 17.4 20.4 21.5 26.4 40.4 49.1
  Psc = 500 MVA 1.17 3.42 5.45 8.49 10.7 13.5 16.8 21.0 17.9 22.2 27.5 34.8 43.0 52.9
cast-resin Psc = 250 MVA 1.14 2.28 3.63 5.63 7.07 8.93 11.1 13.9 17.4 21.5 26.4 33.1 40.4 49.1
  Psc = 500 MVA 1.14 2.28 3.65 5.68 7.14 9.04 11.3 14.1 17.9 22.2 27.5 34.8 43.0 52.9

Psc - Short circuit current at HV windings

Short Circuit Current of Feeders

Short circuit current, Isc at receiving end of a feeder in terms of the short circuit at it's sending end.

Copper 230/400 V

Example of using the table - 10 mm2 cable, 6.5 m in length, upstream fault 35 kA, gives downstream fault of 11 kA

csa (mm²) length of circuit (m)
1.5                           0.8 1 1.3 1.6 3
2.5                         1 1.3 1.6 2.1 2.6 5
4                       0.8 1.7 2.1 2.5 3.5 4 8.5
6                       1.3 2.5 3 4 5 6.5 13
10                   0.8 1.1 2.1 4 5.5 6.5 8.5 11 21
16               0.9 1 1.4 1.7 3.5 7 8.5 10 14 17 34
25             1 1.3 1.6 2.1 2.6 5 10 13 16 21 26 50
35             1.5 1.9 2.2 3 2.5 7.5 15 19 22 30 37 75
50           1.1 2.1 2.7 3 4 5.5 11 21 27 32 40 55 110
70           1.5 3 3.5 4.5 6 7.5 15 30 37 44 60 75 150
95       0.9 1 2 4 5 6 8 10 20 40 50 60 80 100 200
120   0.9 1 1.1 1.3 2.5 5 6.5 7.5 10 13 25 50 65 75 100 130 250
150 0.8 1 1.1 1.2 1.4 2.7 5.5 7 8 11 14 27 55 70 80 110 140 270
185 1 1.1 1.3 1.5 1.6 3 6.5 8 9.5 13 16 32 65 80 95 130 160 320
240 1.2 1.4 1.6 1.8 2 4 8 10 12 16 20 40 80 100 120 160 200 400
300 1.5 1.7 1.9 2.2 2.4 5 9.5 12 15 19 24 49 95 120 150 190 240  
2 x 120 1.5 1.8 2 2.3 2.5 5.1 10 13 15 20 25 50 100 130 150 200 250  
2 x 150 1.7 1.9 2.2 2.5 2.8 5.5 11 14 17 22 28 55 110 140 170 220 280  
2 x 185 2 2.3 2.6 2.9 3.5 6.5 13 16 20 26 33 65 130 160 200 260 300  
3 x 120 2.3 2.7 3 3.5 4 7.5 15 19 23 30 38 75 150 190 230 300 380  
3 x 150 2.5 2.9 3.5 3.5 4 8 16 21 25 33 41 80 160 210 250 330 410  
3 x 185 2.9 3.5 4 4.5 5 9.5 20 24 29 39 49 95 190 240 290 300    
Isc (kA) upstream Isc (kA) downstream
100 94 94 93 92 91 83 71 67 63 56 50 33 20 17 14 11 9 5
90 85 85 84 83 83 76 66 62 58 52 47 32 20 16 14 11 9 4.5
80 76 76 75 75 74 69 61 57 54 49 44 31 19 16 14 11 9 4.5
70 67 67 66 66 64 61 55 52 49 45 41 29 18 16 14 11 5 4.5
60 58 58 57 57 57 54 48 46 44 41 38 27 18 15 13 10 8.5 4.5
50 49 48 48 48 48 46 42 40 39 36 33 25 17 14 13 10 8.5 4.5
40 39 39 39 39 39 37 35 33 32 30 29 22 15 13 12 9.5 8 4.5
35 34 34 34 34 34 33 31 30 29 27 26 21 15 13 11 9 8 4.5
30 30 29 29 29 29 28 27 26 25 24 23 19 14 12 11 9 7.5 4.5
25 25 25 25 24 24 24 23 22 22 21 20 17 13 11 10 8.5 7 4
20 20 20 20 20 20 19 19 18 18 17 17 14 11 10 9 7.5 6.5 4
15 15 15 15 15 15 15 14 14 14 13 13 13 9.5 8.5 8 7 6 4
10 10 10 10 10 10 10 9.5 9.5 9.5 9.5 9 8.5 7 6.5 6.5 5.5 5 3.5
7 7 7 7 7 7 7 7 7 6.5 6.5 6.5 6 5.5 5 5 4.5 4 2.9
5 5 5 5 5 5 5 5 5 5 5 5 4.5 4 4 4 3.5 3.5 2.5
4 4 4 4 4 4 4 4 4 4 4 4 3.5 3.5 3.5 3 3 2.9 2.2
3 3 3 3 3 3 3 3 3 2.9 2.9 2.9 2.8 2.7 2.6 2.5 2.4 2.3 1.9
2 2 2 2 2 2 2 2 2 2 2 2 1.9 1.9 1.8 1.8 1.7 1.7 1.4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.9 0.9 0.9 0.8

Note: for a 3-phase system having 230 V between phases, divide above lengths by 1.732

Aluminium 230/400 V

csa (mm²) length of circuit (m)
2.5                           0.8 1 1.3 1.6 3
4                         1 1.3 1.6 2.1 2.6 5
6                       0.8 1.6 2 2.4 3 8 8
10                       1.3 2.6 3.5 4 5.5 6.5 13
16                   0.8 1.1 2.1 4 5.5 6.5 8.5 11 21
25               0.8 1 1.3 1.7 3.5 6.5 8.5 10 13 17 33
35             0.9 1.2 1.4 1.8 2.3 4.5 9 12 14 18 23 46
50             1.3 1.7 2 2.6 3.5 6.5 13 17 20 26 33 65
70           0.9 1.8 2.3 2.8 3.5 4.5 9 18 23 28 37 46 90
95           1.3 2.5 3 4 5 6.5 13 25 32 38 50 65 130
120         0.8 1.7 3 4 4.5 6.5 8 17 32 40 47 65 80 160
150         0.9 1.7 3.5 4.5 5 7 8.5 17 34 43 50 70 85 170
185       0.9 1 2 4 5 6 8 10 20 40 50 60 80 100 240
240   0.9 1 1.1 1.3 2.5 5 6.5 7.5 10 13 25 50 65 75 100 130 250
300 0.9 1 1.2 1.4 1.5 3 6 7.5 9 12 15 30 60 75 90 120 150 300
2 x 120 0.9 1.1 1.3 1.4 1.6 3 6.5 8 9.5 13 16 32 65 80 95 130 160 320
2 x 150 1 1.2 1.4 1.5 1.7 3.5 7 9 10 14 17 35 70 85 100 140 140  
2 x 185 1.2 1.4 1.6 1.8 2 4.1 8 10 12 16 20 41 80 100 120 160 200  
2 x 240 1.5 1.8 2 2.3 2.5 5 10 13 15 20 25 50 100 130 150 200 250  
3 x 120 1.4 1.7 1.9 2.1 2.4 4.5 9.5 12 14 19 24 48 95 120 140 190 240  
3 x 150 1.5 1.8 2.1 2.3 2.6 5 10 13 15 21 26 50 100 130 150 210 260  
3 x 185 1.8 2.1 2.4 2.7 3 6 12 15 18 24 30 60 120 150 180 240 300  
3 x 240 2.3 2.7 3 3.5 4 7.5 15 19 23 30 38 75 150 190 230 300 380  
Isc (kA) upstream Isc (kA) downstream
100 94 94 93 92 91 83 71 67 63 56 50 33 20 17 14 11 9 5
90 85 85 84 83 83 76 66 62 58 52 47 32 20 16 14 11 9 4.5
80 76 76 75 75 74 69 61 57 54 49 44 31 19 16 14 11 9 4.5
70 67 67 66 66 64 61 55 52 49 45 41 29 18 16 14 11 5 4.5
60 58 58 57 57 57 54 48 46 44 41 38 27 18 15 13 10 8.5 4.5
50 49 48 48 48 48 46 42 40 39 36 33 25 17 14 13 10 8.5 4.5
40 39 39 39 39 39 37 35 33 32 30 29 22 15 13 12 9.5 8 4.5
35 34 34 34 34 34 33 31 30 29 27 26 21 15 13 11 9 8 4.5
30 30 29 29 29 29 28 27 26 25 24 23 19 14 12 11 9 7.5 4.5
25 25 25 25 24 24 24 23 22 22 21 20 17 13 11 10 8.5 7 4
20 20 20 20 20 20 19 19 18 18 17 17 14 11 10 9 7.5 6.5 4
15 15 15 15 15 15 15 14 14 14 13 13 13 9.5 8.5 8 7 6 4
10 10 10 10 10 10 10 9.5 9.5 9.5 9.5 9 8.5 7 6.5 6.5 5.5 5 3.5
7 7 7 7 7 7 7 7 7 6.5 6.5 6.5 6 5.5 5 5 4.5 4 2.9
5 5 5 5 5 5 5 5 5 5 5 5 4.5 4 4 4 3.5 3.5 2.5
4 4 4 4 4 4 4 4 4 4 4 4 3.5 3.5 3.5 3 3 2.9 2.2
3 3 3 3 3 3 3 3 3 2.9 2.9 2.9 2.8 2.7 2.6 2.5 2.4 2.3 1.9
2 2 2 2 2 2 2 2 2 2 2 2 1.9 1.9 1.8 1.8 1.7 1.7 1.4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.9 0.9 0.9 0.8

Note: for a 3-phase system having 230 V between phases, divide above lengths by 1.732



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus

  1. Sinnadurai's avatar Sinnadurai says:
    7/11/2012 11:59 AM

    Give a method of calculating/evaluating fault current contributed by motors(induction/synchrounous)

    • Steven's avatar Steven says:
      7/11/2012 12:44 PM

      IEC 60909 gives some guidelines on how to take into account motor contribution. You can also refer to the following (which gives a guideline on if it is necessary to consider motors):

      http://myelectrical.com/notes/entryid/192/fault-calculations-introduction

      At some stage in the future, I’ll put a post together on this (noted in the my list of future posts).


Comments are closed for this post:
  • have a question or need help, please use our Questions Section
  • spotted an error or have additional info that you think should be in this post, feel free to Contact Us



Random Numbers

Using laser optical pulses the random number generator utilizes the time between arrival of random photos to generate the numbers, ensuring true accuracy...

Cable Trumps

Bored at work and would rather be playing trump card game with you son. The next best thing (or not) maybe the online cable trump card game from AEI Cables...

Cold Fusion (or not?)

Recently I have seen a few interesting articles on viable cold fusion; the combining of atoms at room like temperatures to create boundless energy. Now...

Batteries

A battery consists of one or more cells, each of which use stored chemical energy to produce electrical energy, There are many types of cells and these...

Fault Calculation - Per Unit System

Per unit fault calculations is a method whereby system impedances and quantities are normalised across different voltage levels to a common base.  By removing...

Electromagnetic Fields - Exposure Limits

Exposure to time varying magnetic fields, from power frequencies to the gigahertz range can have harmful consequences.  A lot of research has been conducted...

Welcome back Bottle

‘Kept looking at a card, y’see? Kept looking at it. Welcome back Bottle. Gods below welcome home. The Crippled God A Tale of the Malazan Book of the...

Periodic Electrical Installation Inspection – What to Inspect?

This is the second post in a series of two on periodic electrical inspections. In the first post, I discussed how often inspections should be carried out...

Low Voltage Circuit Breakers

Circuit breakers are switching devices whose primary function is to isolate parts of an electrical distribution system in the even of abnormal conditions...

Tech Topics/Application Notes - Siemens

There are a lot of interesting two page type notes on various medium voltage topics – switchgear, circuit breakers, bus systems etc. It is on the Siemens...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note