Understanding Motor Duty Rating 

By on

One of the comments on my Motor Starting Series was asking for something on duty cycles.  Here it is. 

As a purchaser of a motor, you have responsibility to let the manufacturer know the anticipated duty of the motor.  To assist in the communication of this information, the standard IEC 60034-1 (Rotating electrical machines) defines several duty characteristics, denoted S1 to S10:

S1  Continuous duty The motor operates at a continuous load for sufficient time to enable machine to reach thermal equilibrium. 
S2 Short Time duty Operation at a load for a time not sufficient to reach thermal equilibrium, followed by enough time for the motor to cool down.
S3  Intermittent periodic duty
Series of identical duty cycles each a constant load for a period, followed by a rest period. Thermal equilibrium is not reached during the cycle.
S4 Intermittent periodic duty with starting Similar to S3, but there is a significant starting time within the periodic operation.
S5 Intermittent periodic duty with electric braking Sequence of identical duty cycles - starting, operation, braking and rest.  Again thermal equilibrium is not reached.
S6 Continuous operation periodic duty Identical duty cycles with a period at load followed by a period at no load.  Difference between S1 is that the motor runs at no-load, without actual stopping.
S7 Continuous operation periodic duty with electric braking As per S6, but with a significant starting and electric breaking periods.  Again motor operates at no-load for  period instead of stopped. 
S8 Continuous operation periodic duty with related load/speed changes Series of identical repeating duty cycles, where within each cycle the motor operates at several different load levels and speed. There is not stopped time and thermal equilibrium is not reached.
S9 Duty with non-periodic load and speed variations     Load and speed vary periodically within the permissible operating range. Frequent overloading may occur.
S10 Duty with discrete constant loads and speeds Duty with discrete number of load/speed combinations, with these maintained long enough to reach thermal equilibrium.
     

 

Thermal Equilibrium is the state reached when the temperature rise of the machine does not vary by more than 2K per hour.   If you don't specify the duty cycle, the manufacturer will likely assume S1. Click on the image to see a larger version, illustrating the duty cycles.

If anyone has anything to add, please do so below. 



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus

  1. sabari nath's avatar sabari nath says:
    5/24/2013 7:51 AM

    Can you help me understand the relation between Motor duty cyce and Starts per hour?


Comments are closed for this post:
  • have a question or need help, please use our Questions Section
  • spotted an error or have additional info that you think should be in this post, feel free to Contact Us



How to measure power supply quality

If your are ever called out to troubleshoot something on your electrical system, one of the first things consider is the supply voltage. You want to ensure...

Welcome back Bottle

‘Kept looking at a card, y’see? Kept looking at it. Welcome back Bottle. Gods below welcome home. The Crippled God A Tale of the Malazan Book of the...

Sony Pocket eBook Reader

For the past few years I have reading eBooks on my HTC touch phone. On and off I have debated buying an eReader and recently purchased a Sony PRS-300 ...

New Mail Chimp

We've been sending out Newsletters on a regular basis for a few weeks now. To do this we have been using Google's Feedburner service. While Feedburner...

Voltage Levels – Confused?

I was having a conversation the other day about voltage levels.  While everyone was in agreement that low voltage was 1000 V and less, there was more confusion...

Software Usage Guidelines

Using software in our  work is essential for most of us and we are becoming even more dependant on it's use.  While software is a great asset, many times...

Batteries

A battery consists of one or more cells, each of which use stored chemical energy to produce electrical energy, There are many types of cells and these...

Why is electricity so hard to understand?

It's been a busy few months on different projects or busy couple of decades depending on how I look at it. I can say that on the odd (frequent) occasion...

Electromagnetic Fields - Exposure Limits

Exposure to time varying magnetic fields, from power frequencies to the gigahertz range can have harmful consequences.  A lot of research has been conducted...

Power Factor

Power factor is the ratio between the real power (P in kW) and apparent power (S in kVA) drawn by an electrical load. The reactive power (Q in kVAr)...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note