Understanding Motor Duty Rating 

By on

One of the comments on my Motor Starting Series was asking for something on duty cycles.  Here it is. 

As a purchaser of a motor, you have responsibility to let the manufacturer know the anticipated duty of the motor.  To assist in the communication of this information, the standard IEC 60034-1 (Rotating electrical machines) defines several duty characteristics, denoted S1 to S10:

S1  Continuous duty The motor operates at a continuous load for sufficient time to enable machine to reach thermal equilibrium. 
S2 Short Time duty Operation at a load for a time not sufficient to reach thermal equilibrium, followed by enough time for the motor to cool down.
S3  Intermittent periodic duty
Series of identical duty cycles each a constant load for a period, followed by a rest period. Thermal equilibrium is not reached during the cycle.
S4 Intermittent periodic duty with starting Similar to S3, but there is a significant starting time within the periodic operation.
S5 Intermittent periodic duty with electric braking Sequence of identical duty cycles - starting, operation, braking and rest.  Again thermal equilibrium is not reached.
S6 Continuous operation periodic duty Identical duty cycles with a period at load followed by a period at no load.  Difference between S1 is that the motor runs at no-load, without actual stopping.
S7 Continuous operation periodic duty with electric braking As per S6, but with a significant starting and electric breaking periods.  Again motor operates at no-load for  period instead of stopped. 
S8 Continuous operation periodic duty with related load/speed changes Series of identical repeating duty cycles, where within each cycle the motor operates at several different load levels and speed. There is not stopped time and thermal equilibrium is not reached.
S9 Duty with non-periodic load and speed variations     Load and speed vary periodically within the permissible operating range. Frequent overloading may occur.
S10 Duty with discrete constant loads and speeds Duty with discrete number of load/speed combinations, with these maintained long enough to reach thermal equilibrium.
     

 

Thermal Equilibrium is the state reached when the temperature rise of the machine does not vary by more than 2K per hour.   If you don't specify the duty cycle, the manufacturer will likely assume S1. Click on the image to see a larger version, illustrating the duty cycles.

If anyone has anything to add, please do so below. 



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus

  1. sabari nath's avatar sabari nath says:
    5/24/2013 7:51 AM

    Can you help me understand the relation between Motor duty cyce and Starts per hour?


Comments are closed for this post:
  • have a question or need help, please use our Questions Section
  • spotted an error or have additional info that you think should be in this post, feel free to Contact Us



Difference Between Live and Dead Tank Circuit Breakers

A quick post in connection with an email question: Live Tank - the circuit breaker the switching unit is located in an insulator bushing which is live...

Electromagnetic Fields - Exposure Limits

Exposure to time varying magnetic fields, from power frequencies to the gigahertz range can have harmful consequences.  A lot of research has been conducted...

Earth Electrode Resistance

Earthing of electrical systems is essential for the correct functioning and the protecting of life and equipment in the event of faults.  The earth electrode...

Low Voltage Switchroom Design Guide

Low voltage (LV) switchrooms are common across all industries and one of the more common spatial requirements which need to be designed into a project...

Voltage Drop in Installations - Concepts

Problems on achieving maximum voltage drop within an installation come up often. Depending where you live, local regulations will have different limits...

HTML Symbol Entities

HTML supports a variety of entity symbols which can be entered using either numbers or an entity name.  The number or name is preceded by the ‘&’ sign...

IEC Document Designation

Often document control is dictated by project requirements, for example a particular organisation may have an existing numbering system. Existing company...

Generation of a Sine Wave

A fundamental concept behind the operation of alternating current systems is that voltage and current waveforms will be sinusoidal – a Sine Wave. This...

Resistors

Resistors are electronic components that oppose the flow of current.  Manufactured in various types and ranges they have a wide application to electronics...

Periodic Electrical Installation Inspection – How Often?

How often installations are inspected is up to the owner of the installation, provided such durations do not exceed any regulatory maximums in force. ...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note