Alternating current (a.c.) is the backbone of modern electrical power distribution.  In this article I’ll be pulling some of the more important concepts together.  It is a work in progress and I’ll be adding to it bit by bit as I start closing pages down in the Wiki.  Hopefully by the time the Wiki is fully depreciated, we should have a reasonable article here. 

Alternating Current Theory

Sinewave
Sine wave
Alternating voltage or current is in the form of a sine wave and is given by:

myElectrical Equation 

and

myElectrical Equation 

 

Where:
V(t) - is the instantaneous voltage at time, t
I(t) - is the instantaneous voltage at time, t
Vm - is the maximum value of instantaneous voltage
Im - is the maximum value of instantaneous current
ω - is the angular frequency in radians
myElectrical Equation - is the phase angle of the voltage
myElectrical Equation - is the phase angle of the current

The number of full cycles per second is the frequency (f) and is measured in Hertz (Hz).  The period (T) of a sine wave is the time to complete on cycle in seconds and is related to the frequency by:

myElectrical Equation

Note: In the Europe, the frequency is 50 Hz (period to 20 mS), while in the US it is 60 Hz (period 16.67 mS).

The angular frequency ω, is given by:

image00

RMS and Average Values

The average voltage or current of a pure sine wave is zero.

Even though the average is zero the power delivered by an AC source is not zero.

The root-mean-square (rms) values of current voltage and current equate the power delivered by the AC circuit.

myElectrical Equation

The average value of a sine wave is 0.637 of the maximum.

RMS Theory

The RMS value of a function is the root of the mean of the square of the function. This is expressed mathematically as:

  I RMS = 1 2T 0 2T i (2) 2 dt

In electrical engineering this is important as it relates to a value of voltage (V) or current (I), which when multiplied together gives power:

2d107b24f126e238f558cb2bc58045ca

The RMS value can be worked out for any periodic function. For common electrical waveforms this gives:

    RMS Value
Sine Wave myElectrical Equation myElectrical Equation
Square Wave myElectrical Equation myElectrical Equation
Saw-tooth Wave myElectrical Equation myElectrical Equation

Complex Power

Real, reactive power and power factor can be explained using different concepts.  Sometimes it is convenient to use the concept of complex power.  In an electrical system, if the voltage and current are treated as vectors, these can be expressed in complex numbers.  The complex power S, of the system is then given by:

  S=V I *

where:
P is the complex power in VA
V is the voltage in complex form in V
I* is the conjugate of the current in complex form (the imaginary part is multiplied by -1) in A

ComplexPower
Complex Power
Complex power S, is a vector and is commonly represented as:

  S=P+jQ

where:
S is the complex power in VA
P is the real power transmitted in W
Q is the reactive power transmitted in VAr
j is the complex operator √-1

The quantity P, represents the real power transmitted in the system.  This is the power that actually does work (i.e. rotating motors, heating homes, etc.).  The reactive power Q, does not do actual real work, but is responsible for maintaining the magnetic and electric fields of the electrical system.  These fields provided the energy storage mechanisms necessary for the distribution system to work. The magnitude of the complex power S, is often referred to as apparent power.

The ratio between the real and apparent power is the power factor of a system:

  power factor= P |S|

  P=|S|× power factor

  Q= |S| 1p f 2

If the current is lagging the voltage in phase (for example in an inductive circuit) the power factor is said to be lagging.  Conversely if the current leads the voltage the power factor is said to be leading.  For a power factor of 1, the real and apparent power will be the same, with the reactive power being equal to zero.  As the power factor is reduce, more reactive power in the system is required.  Generation of reactive power required additional equipment,  increasing transmission system costs and operating energy loss.  By ensuring high power factors these costs and loses are reduced.

AC System Components

The three main components to an alternating current (ac) system are resistance, inductance and capacitance.

Resistance

The resistance of an alternating current circuit is denoted by the symbol R.

Inductance

The impedance of a inductor XL is given by:

12040301

where:
myElectrical Equation - is the angular frequency
f - is the frequency
L - is the inductance in henry, H
j - is the imaginary unit

Q-factor of an Inductor

While in an ideal inductor the resistance is zero, in practice there is always some resistance. Loss in the resistance makes the inductor inefficient.  The ratio of inductive reactance to resistance is the Q-factor; the higher the value the closer to an ideal conductor:

  Q= ωL R

For more on inductance, see the Notes Post on Inductance

Capacitance

The impedance of a capacitor Xc is given by:

myElectrical Equation

where:
C - is the capacitance in Farad

See also: Capacitor Theory 

 

Impedance of a Circuit

Impedance (Z) is the resistance in ohms (Ω)  to the flow of electric current in a circuit:

image01

where:
R - is the resistance of the circuit, Ω
X - is the reactance of the circuit,  Ω

Note: Admittance (Y) is the inverse of impedance (i.e. Y=1/Z).  The unit of admittance is the siemens (S)

References

  • [1] William D.Stevenson, "Elements of Power System Analysis", McGraw-Hill, 1982
  • [2] The IDC Engineers Pocket Guide, First Edition, Volume 5


Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus



Contribute to myElectrcial

Have an opinion or something to say, want to ask or answer questions, share your knowledge then use our site to do it . As a community of people interested...

Hazardous Areas – IEC and NEC/CEC Comparison

Depending where in the world you work, you are likely following one of two standards International Electrotechnical Commission (IEC) National...

Photovoltaic (PV) - Utility Power Grid Interface

Photovoltaic (PV) systems are typically more efficient when connected in parallel with a main power gird. During periods when the PV system generates energy...

UPS - Uninterruptible Power Supply

A UPS is an uninterruptible power supply.  It is a device which maintains a continuous supply of electrical power, even in the event of failure of the...

Fault Calculations - Introduction

Fault calculations are one of the most common types of calculation carried out during the design and analysis of electrical systems. These calculations...

Control Theory

Control theory looks at how systems work and are controlled from a mathematical view.  This note gives a brief introduction to some of the concepts – more...

IEC Reference Designations

The IEC publishes a series of documents and rules governing the preparation of documents, drawings and the referencing of equipment.   Depending on country...

Laplace Transform

Laplace transforms and their inverse are a mathematical technique which allows us to solve differential equations, by primarily using algebraic methods...

The ac resistance of conductors

In a previous article I looked at the dc resistance of conductors and in this article we turn our attention to ac resistance. If you have not read the...

IEC 60287 Current Capacity of Cables - An Introduction

IEC 60287 "Calculation of the continuous current rating of cables (100% load factor)" is the International Standard which defines the procedures and equations...