Lighting Design - An Introduction 

By on

    From the earliest times, humans have found ways to create light. Pre-historic peoples used natural materials (moss, grass, etc.) soaked in animal fat and then ignited. Around 3000 to 4500 BC, oil lamps and then candles were invented. During the 18th and early 19th centuries, the technology of oil lamps improved and gas lighting was developed.  Starting in the middle of the 19th century, electrical lighting became available with the invention of the fluorescent and incandescent lamps.

    Technology has continued to improve and today we see the massive use of electrical lighting in the form of fluorescent, mercury and sodium vapor, metal halide and light emitting diodes (LED). Technology is continuing to develop with the latest developments being the introduction of magnetic induction and sulfur lamps.

    Lighting design is the field of creating light, its application and use by people.   Lighting design starts by developing the objectives and then quantifying these by specifying the criteria. When looking objectives, the lighting designer will consider:

    • day lighting and how it is used
    • types of artificial lighting to be considered
    • required light levels and uniformity
    • types and methods of lighting control
    • maintenance of the slighting system
    • the efficiency goals of the lighting system

    Lighting Levels

    A key consideration of the lighting design is the selection of illuminance values and required uniformity.  Typically reference is made to tables in local design guides. Values given in the table are not mandatory and individual considerations may give need to adjust these values.

    Lighting Software

    During recent years, the use of lighting design software has become standard practice. Most software involves modelling a physical representation of the area to be lit, selecting the fittings and looking at the light distribution.

    Software will contain luminaire data from a variety of manufacturers. Where particular manufacturers luminaires are missing from the software, data files for these can generally be downloaded from the luminaire manufacturers website and imported into the lighting software.

    Links to come free and paid for lighting software can be found at:

    AGi32CanberraAirport

    AGi32 rendering of lounge at
    Canberra Airport

    Lumen Method

    Prior to the use of lighting software, the Lumen method, was commonly used to calculate the required number of fitting for rectangular arrays. In the method the average Illuminance E(s) over a reference surface s is given by:

    myElectrical Equation

    where:

      • F -  is the initial lamp lumen, lm
      • n  - is the number of lamps per Luminaire
      • N -  is the number of luminaires
      • LLF - is the light loss factor
      • UF(s) -  is the utilisation factor for the reference surface, s

    F is the initial lamp lumens. Light output reduction during the lamp life being included in the light loss factor.

    Lumen CalculationUF(s) measures of the efficiency of the lighting scheme considering light on the working plane to consist of direct light and reflected light.   While it can be calculated, UF(s) is more commonly looked up from manufacturers tables.  Tables will list UF(s) for differing wall, ceiling cavity and floor cavity reflectance's and the room index.  The room index RI, is dependant on the room  geometry and given by:

    myElectrical Equation 

    Note: for different shapes, RI is calculated by dividing the room into two or more rectangular sections.

    When using manufacturers tables with the Lumen method, utilisation factor tables, typically include maximum Spacing to Height Ratio (SHR) for the luminaire.  Adhering to SHR ratios, will ensure some level of uniformity of the Illuminance.

    Glare

    Excessive contracts in illuminance can result in glare, resulting in discomfort is a reduction in the ability to see or perform a task.  There are a variety of ways to calculate glare – common ones being the Unified Glare Rating (UGR) for interiors, Glare Rating (GR) for outdoor areas and sports venues and the Threshold Increment (TI) for street  lighting.

    As with illuminance values, recommended glare ratings can be found in tables in local design guides.  Depending on area values for UGR typically range from 16 to 28, GR from 45 to 70 and TI from 10 to 15.



    Steven McFadyen's avatar Steven McFadyen

    Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

    myElectrical Engineering

    comments powered by Disqus



    A mechanical engineering paper, some history and memories

    I was digging in my bookshelf and came across the 80th Anniversary Association of Mine Resident Engineers, Papers and Discussions Commemorative Edition...

    Useful Motor Technical Information

    Sometimes it’s useful to be able to quickly lookup a piece of technical information.  This note is a collection of information related to motors, and in...

    Fault Calculation - Symmetrical Components

    For unbalance conditions the calculation of fault currents is more complex. One method of dealing with this is symmetrical components. Using symmetrical...

    How a Digital Substation Works

    Traditionally substations have used circuit breakers, current transformers (CT), voltage transformers (VT) and protection relays all wired together using...

    Cable Sizing Software

    When sizing cables nearly, everyone uses some form of software. This ranges from homespun spreadsheets to complex network analyses software. Each has its...

    3 Phase Loads

    Three phase systems are derived from three separate windings, either connected in delta or star (wye). Each winding can be treated separately, leading...

    Understanding LV Circuit Breaker Fault Ratings

    I think this post is going to be helpful to several of our readers. While the IEC low voltage circuit breaker Standard [IEC 60947-2, Low voltage switchgear...

    Lightning Risk Assessment (IEC 62305)

    IEC 62305 'Protection against lightning' requires a risk assessment be carried out to determine the characteristics of any lightning protection system...

    Understanding Circuit Breaker Markings

    IEC 60947 is the circuit breaker standard and covers the marking of breakers in detail. Any manufacturer following this standard should comply with the...

    Load Flow Study – how they work

    A load flow study is the analysis of an electrical network carried out by an electrical engineer. The purpose is to understand how power flows around...

    Have some knowledge to share

    If you have some expert knowledge or experience, why not consider sharing this with our community.  

    By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

    To get started and understand our policy, you can read our How to Write an Electrical Note