Lighting Design - An Introduction 

By on

    From the earliest times, humans have found ways to create light. Pre-historic peoples used natural materials (moss, grass, etc.) soaked in animal fat and then ignited. Around 3000 to 4500 BC, oil lamps and then candles were invented. During the 18th and early 19th centuries, the technology of oil lamps improved and gas lighting was developed.  Starting in the middle of the 19th century, electrical lighting became available with the invention of the fluorescent and incandescent lamps.

    Technology has continued to improve and today we see the massive use of electrical lighting in the form of fluorescent, mercury and sodium vapor, metal halide and light emitting diodes (LED). Technology is continuing to develop with the latest developments being the introduction of magnetic induction and sulfur lamps.

    Lighting design is the field of creating light, its application and use by people.   Lighting design starts by developing the objectives and then quantifying these by specifying the criteria. When looking objectives, the lighting designer will consider:

    • day lighting and how it is used
    • types of artificial lighting to be considered
    • required light levels and uniformity
    • types and methods of lighting control
    • maintenance of the slighting system
    • the efficiency goals of the lighting system

    Lighting Levels

    A key consideration of the lighting design is the selection of illuminance values and required uniformity.  Typically reference is made to tables in local design guides. Values given in the table are not mandatory and individual considerations may give need to adjust these values.

    Lighting Software

    During recent years, the use of lighting design software has become standard practice. Most software involves modelling a physical representation of the area to be lit, selecting the fittings and looking at the light distribution.

    Software will contain luminaire data from a variety of manufacturers. Where particular manufacturers luminaires are missing from the software, data files for these can generally be downloaded from the luminaire manufacturers website and imported into the lighting software.

    Links to come free and paid for lighting software can be found at:

    AGi32CanberraAirport

    AGi32 rendering of lounge at
    Canberra Airport

    Lumen Method

    Prior to the use of lighting software, the Lumen method, was commonly used to calculate the required number of fitting for rectangular arrays. In the method the average Illuminance E(s) over a reference surface s is given by:

    myElectrical Equation

    where:

      • F -  is the initial lamp lumen, lm
      • n  - is the number of lamps per Luminaire
      • N -  is the number of luminaires
      • LLF - is the light loss factor
      • UF(s) -  is the utilisation factor for the reference surface, s

    F is the initial lamp lumens. Light output reduction during the lamp life being included in the light loss factor.

    Lumen CalculationUF(s) measures of the efficiency of the lighting scheme considering light on the working plane to consist of direct light and reflected light.   While it can be calculated, UF(s) is more commonly looked up from manufacturers tables.  Tables will list UF(s) for differing wall, ceiling cavity and floor cavity reflectance's and the room index.  The room index RI, is dependant on the room  geometry and given by:

    myElectrical Equation 

    Note: for different shapes, RI is calculated by dividing the room into two or more rectangular sections.

    When using manufacturers tables with the Lumen method, utilisation factor tables, typically include maximum Spacing to Height Ratio (SHR) for the luminaire.  Adhering to SHR ratios, will ensure some level of uniformity of the Illuminance.

    Glare

    Excessive contracts in illuminance can result in glare, resulting in discomfort is a reduction in the ability to see or perform a task.  There are a variety of ways to calculate glare – common ones being the Unified Glare Rating (UGR) for interiors, Glare Rating (GR) for outdoor areas and sports venues and the Threshold Increment (TI) for street  lighting.

    As with illuminance values, recommended glare ratings can be found in tables in local design guides.  Depending on area values for UGR typically range from 16 to 28, GR from 45 to 70 and TI from 10 to 15.



    Steven McFadyen's avatar Steven McFadyen

    Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

    myElectrical Engineering

    comments powered by Disqus



    ABB Technical Guides - Motor Operation

    ABB has produced a range of technical guides that offer concise explanations of the major technologies and technical issues in low voltage AC drives. ...

    Fault Calculations - Introduction

    Fault calculations are one of the most common types of calculation carried out during the design and analysis of electrical systems. These calculations...

    Skin Tapping Input

    Tapping your forearm or hand with a finger could soon be the way you interact with gadgets. A new technology created by Microsoft and Carnegie Mellon ...

    Tip – Latitude and Longitude on Large Scale Plans

    If you are working on a large plan, get the real coordinates [latitude, longitude] for two or more points and add them to the drawing. That way you can...

    Smarter Electrical Distribution

    The other day I came across an article in Technology Review on the development of a smart transformer. A professor at North Carolina State University is...

    Periodic Electrical Installation Inspection – What to Inspect?

    This is the second post in a series of two on periodic electrical inspections. In the first post, I discussed how often inspections should be carried out...

    Back to basics - the Watt (or kW)

    When thinking about watts (W) or kilowatt (kW = 1000 W) it can be useful too keep in mind the fundamental ideas behind the unit. Watt is not a pure electrical...

    Cable Sheath and Armour Loss

    When sizing cables, the heat generated  by losses within any sheath or armour need to be evaluated. When significant, it becomes a factor to be considered...

    8 Motor parts and common faults

    Straight forward list of some common motor faults.  If I have missed any other common faults, please take a bit of time to add them in as a comment below...

    What is an Open Delta Transformer

    In three phase systems, the use of transformers with three windings (or legs) per side is common.  These three windings are often connected in delta or...