Fault Calculations - Typical Equipment Parameters 

By on

A frequent problem in fault calculations is the obtaining of equipment parameters. While it is always preferable to use the actual parameters of the equipment, sometimes these are not available. In this instance it is necessary to resort to the use of typical parameters.

This note is intended to become a collection of typical parameters. If there is something missing or needs adding, please leave a comment in the discussion.

HV Network Impedance

Impedance of HV network referred to LV side of transformer

Psc Uo (V) Ra (mΩ) Xa (mΩ)
250 MVA 420 0.106 0.71
500 MVA 420 0.053 0.353

Low Voltage Power Transformers

Transformer Short Circuit Impedance

Typical values short circuit impedance, USC for different kVA ratings (HV winding < 20 kV)

  Type of Transformer
transformer rating oil-immersed cast-resin
50 to 630 4% 6%
800 to 2500 6% 6%

Transformer Impedance (400 V)

Resistance, reactance and impedance for typical transformers (HV winding <20 kV)

transformer rated power (kVA) 50 100 160 250 315 400 500 630 800 1000 1250 1600 2000 2500
oil-immersed Usc % 4 4 4 4 4 4 4 4 6 6 6 6 6 6
  Rtr 95.3 37.9 16.2 9.2 6.9 5.1 3.9 2.9 2.9 2.3 1.8 1.4 1.1 0.9
  Xtr 104.1 59.5 41.0 26.7 21.3 16.9 13.6 10.8 12.9 10.3 8.3 6.5 5.2 4.1
  Ztr 141.1 70.5 44.1 28.2 22.4 17.7 14.1 11.2 13.2 10.6 8.5 6.6 5.3 4.2
cast-resin Usc % 6 6 6 6 6 6 6 6 6 6 6 6 6 6
  Rtr   33.5 18.6 10.7 8.2 6.1 4.6 3.5 2.6 1.9 1.5 1.1 0.8 0.6
  Xtr   100.4 63.5 41.0 32.6 25.8 20.7 16.4 13.0 10.4 8.3 6.5 5.2 4.2
  Ztr   105.8 66.2 42.4 33.6 26.5 21.2 16.8 13.3 10.6 8.4 6.6 5.3 4.2

 

Synchronous Machines

Performance Under Fault Conditions

Sub-transient emf:  myElectrical Equation

Transient emf:  myElectrical Equation 

Synchronous emf:  myElectrical Equation
Fault current: myElectrical Equation

Typical Machine Reactances

Typical Machine Reactances (& Time Constants

  Cylindrical Rotor
Turbine Generators

Salient Pole Generators
  Salient Pole
Synchronous
Condensers

Conventional
Direct
Cooled

4 Pole

Multi-Pole
Synchronous
Direct axis Xd pu 1.6-2.0 0.8-1.0 2.0-2.3 2.1-2.4 1.3-2.1 1.3-1.5
Quadrature axis Xq pu 1.0-1.25 0.5-0.65 1.95-2.1 1.95-2.25 0.6-1.2 0.8-1.0
Transient
Reactance  Xd' pu 0.3-0.5 0.2-0.35 0.18-0.25 0.27-0.30 0.15-0.35 0.4-0.5
Short circuit τd' s 1.5-2.5 1.0-2.0 0.75-1.0 0.75-1.0 0.8-1.2 0.8-1.2
Open circuit τdo' s 5-10 3-7 4-8 6-9.5 4-8 3-7
Sub-transient
Direct axis Xd'' pu 0.2-0.4 0.12-0.25 0.11-0.13 0.19-0.23 0.1-0.25 0.2-0.35
Quadrature axis Xq'' pu 0.25-0.6 0.15-0.45 0.11-0.13 0.19-0.23 0.14-0.35 0.2-0.35
Short circuit - direct axis τd' s 0.04-0.09 0.05-0.10 0.015-0.025 0.02-0.03 0.02-0.04 0.02-0.07
Open circuit - direct axis τd'' s 0.07-0.11 0.08-0.25 0.015-0.025 0.02-0.03 0.04-0.07 0.02-0.07
Short circuit - quadrature axis τq'' s 0.04-0.6 0.05-0.6 0.015-0.025 0.02-0.03 0.10-0.15 0.02-0.07
Open circuit - quadrature axis τq0'' s 0.1-1.2 0.2-0.9 0.015-0.025 0.02-0.03 0.3-0.7 0.1-0.2
Other Reactances
Negative sequence X-ve pu 0.25-0.5 0.14-0.35 0.11-0.13 0.19-0.23 0.12-0.3 0.2-0.35
Zero sequence  Xo pu 0.12-0.16 0.06-0.10 0.05-0.075 0.11-0.16 0.03-0.10 0.1-0.2

Cables

myElectrical Equation
myElectrical Equation

where:

d = distance between centre
r = geometric mean radius
a = cross sectional area (mm)

TypicalEquipmentCables



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus



myElectrical - Cable Sizing Tool Upgrade

Our IEE cable sizing was wrote a few years ago and had become rough around the edges. I thought it was time to give the tool a service. Unfortunately when...

3 Phase Loads

Three phase systems are derived from three separate windings, either connected in delta or star (wye). Each winding can be treated separately, leading...

Fault Calculations - Typical Equipment Parameters

A frequent problem in fault calculations is the obtaining of equipment parameters.  While it is always preferable to use the actual parameters of the equipment...

Gas Insulated or Air Insulated Switchgear

Various arguments exist around SF6 Gas Insulated (GIS) and Air Insulated (AIS) medium voltage switchgear. Recently we had to change a GIS design to AI...

Back to Basics - Ohm’s Law

Electrical engineering has a multitude of laws and theorems. It is fair to say the Ohm's Law is one of the more widely known; it not the most known. Developed...

Lighting Design - An Introduction

From the earliest times, humans have found ways to create light. Pre-historic peoples used natural materials (moss, grass, etc.) soaked in animal fat and...

What does N+1 mean?

The term 'N+1' relates to redundancy and simply means that if you required 'N' items of equipment for something to work, you would have one additional...

Lighting - Lamps

Lamps are the essential part of any luminaire. These are the light generating components. Since the advent of electrical lighting in the middle of the...

9 power supply issues solved by using a UPS

Installation of a UPS can help in reducing problems due to issues with the power supply.  A lot of people relate this to nine key issues.  Depending on...

Electromechanical Relays

Electromechanical relays have been the traditional backbone of electrical protection systems.  While over recent years these have been replaced by microprocessor...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note