Motor Insulation 

By on

Insulation on a motor prevents interconnection of windings and the winding to earth. When looking at motors, it is important to understand how the insulation functions and its practical application.

Rating

motorInsulationClass
Motor Insulation Class

IEC 60085 ‘Electrical insulation - Thermal evaluation and designation ’ divides insulation into classes. Each class is given a designation that corresponds to the upper temperature limit of the insulating material when used under normal operating conditions.

The correct insulation of the winding of a motor is determined by both the temperature rise in the motor and the temperature of the ambient air.

If a motor is subjected to an ambient temperature higher than 40o C, it must normally be de-rated or a higher insulation class of material used.

Note: motors are typically rated for class 'B' or 'F' insulation

Tip: specify a class ‘F’ insulation, but a class ‘B’ temperature rise.  This gives a 25o C margin – can be used for high ambient temperatures for example.

IEC – NEMA Temperature Rise

The table below compares the IEC temperature rise ratings, with the NEMA specification:

Insulation
Class 
  IEC   NEMA
[1.0 SF]
NEMA
[1.5 SF] 

A

60

60

70

E

75

-

-

B

80

80

90

F

100

105

115

H

125

125

-

* SF - NEMA Service Factor

Insulation Life and Temperature

If the upper temperature limit of the insulation material is exceeded the life of the insulation will be reduced at illustrated below.

The selection of insulation class is critical to the life of the motor.  A common rule of thumb is that the life of the motor insulation will be halved for every 8 to 10 °C it is operated above the rated insulation temperature

motorInsulationLifeTime
Motor Life and Temperature

Testing Insulation

Prior to putting the motor into operations, during routine maintenance and fault finding an insulation tester is used to measure the motor insulation and verify it’s suitability.

Insulation Test Voltages

Motor Voltage (V) DC Test Voltage (V)
< 2000 500
2001 - 4000 1000 *
4001 - 8000 2500 *
8001 - 16000 5000 *

Check Resistance First Using 500 V 

Recommended Winding Resistance Values

Given a line to line voltage V (kV), winding temperature T (oC) then the minimum insulation resistance (MΩ) of the complete winding should be greater than: 

{R_w} - \left( {V + 1} \right){e^{k - 0.692\,T}}

k = 4.159 for a new machine, clean, dry
k = 2.869 for aged machine, clean, uncontaminated
k = 2.771 machine after several years, normal industrial pollution

On a three phase winding the resistance of each phase:

{R_{ph}} = 2{R_w}

Polarisation Index

motorDryingOutProcess
Motor Drying Out Process

The polarisation index is the ratio of the winding insulation resistance measured after applying the test voltage for 10 minutes to the value obtained after 1 minute and is used as a guide to the dryness of the winding.

{\rm{Polarisation Index }} = \frac{{{R_{10}}}}{{{R_`}}}

A clean dry winding will typically give a value greater than 1.5. The lower the ratio the greater the leakage path to ground (in effect the capability of the insulation to hold a capacitive charge).

No exact cut-off values exist (1.25 to 2.5 being common). The best guide is a constant ratio over successive readings taken periodically



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus



Low Voltage Circuit Breakers

Circuit breakers are switching devices whose primary function is to isolate parts of an electrical distribution system in the even of abnormal conditions...

Large Hadron Collider

The 27 km, Euro 6 billion  Collider lies on the border between France and Switzerland, took nearly 30 years to complete.  Some of the lofty goals for the...

IEC Document Designation

Often document control is dictated by project requirements, for example a particular organisation may have an existing numbering system. Existing company...

UPS - Uninterruptible Power Supply

A UPS is an uninterruptible power supply.  It is a device which maintains a continuous supply of electrical power, even in the event of failure of the...

Famous Scientists

Here’s list of some famous scientists. Deliberately short, with the aim to provide a quick memory jog or overview. If your looking for more detailed information...

Fault Calculations - Introduction

Fault calculations are one of the most common types of calculation carried out during the design and analysis of electrical systems. These calculations...

Electric Motors

Collection of links to various places with useful motor information. I’ll try and return to the page every now and again to update it with any motor notes...

E-Ink

Before the technical, some general information. E-ink display are found in a lot of e-readers, some mobile phones and similar devices and the intent is...

Introduction to Cathodic Protection

If two dissimilar metals are touching and an external conducting path exists, corrosion of one the metals can take place.  Moisture or other materials...

Fault Calculations - Typical Equipment Parameters

A frequent problem in fault calculations is the obtaining of equipment parameters.  While it is always preferable to use the actual parameters of the equipment...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note