myElectrical - Cable Sizing Tool Upgrade 

By on

Our IEE cable sizing was wrote a few years ago and had become rough around the edges.  I thought it was time to give the tool a service.  Unfortunately when I looked under the hood I found cracked cylinders, broken bell ends and worn cylinders.  Rather than a quick service I had no choice be to do a major rewrite on the software.  The only thing I didn't touch is the chassis [database], which while suffering from patches of rust, was still usable.

In rewriting the software good things have happened.  There has been a large increase in performance [no more very long waits, with frequent postbacks] and I have put in a couple of enhancements.  The main things users will notice are:

 

  • things should be a lot quicker.  The number of postbacks has been minimized (unfortunately a few are required to retrieve cable configuration data).  Calculation of the cable size itself has been improved to make the processing more efficient.
  • everything is all on one page.  A slicker user interface with no more switching between tabs.
  • you now have quick access to the underlying data.  Click any of the  'i' buttons on the form and the relevant data table should pop up.

Of all the software tools on the site, the cable sizing one is the most complex.  A lot of the complexity derives from strictly following the Wiring Regulations, which while designed for humans to work through, are not necessarily software friendly.  Hopefully the tool should be working well, but if you do come across and bugs or have any suggestions, please let me know.

Click here to  give the Cable Sizing Tool a try.



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus

  1. skalooba76's avatar skalooba76 says:
    12/7/2011 9:49 AM

    hi,

    i noticed when i try to size cable for small load, the software keep giving the wrong size, i.e for 12 Amp load, 380V, protected by 16 Amp, the cable calculation software will give 35mm2 which is wrong.

    please look into this matter

    thanks for all the help

    niki

    • Steven's avatar Steven says:
      12/7/2011 10:25 AM

      It may be the fault level. In calculating the size the following happens:

      Cable is calculated on current capacity
      Voltage drop is calculated (and cable size increased if necessary)
      Fault level withstand is calculated (and cable size increased if necessary)

      I have just tried your scenario (with XLPE cable) and at 25kA fault, 25m2 was required, but at 1kA fault only 1mm2.


Comments are closed for this post:
  • have a question or need help, please use our Questions Section
  • spotted an error or have additional info that you think should be in this post, feel free to Contact Us



Restricted Earth Fault Protection

The windings of many medium and small sized transformers are protected by restricted earth fault (REF) systems. The illustration shows the principal of...

Voltage Levels – Confused?

I was having a conversation the other day about voltage levels.  While everyone was in agreement that low voltage was 1000 V and less, there was more confusion...

UPS - Uninterruptible Power Supply

A UPS is an uninterruptible power supply.  It is a device which maintains a continuous supply of electrical power, even in the event of failure of the...

Arc Flash Calculations

Working in the vicinity of electrical equipment poses an hazard. In addition to electric shock hazard, fault currents passing through air causes Arc Flash...

1,000 kV UHV First for China

At the beginning of the year China put the world's first 1,000 kV UHV transmission system into operation. Transmitting power at over a million volts is...

How to Size Current Transformers

The correct sizing of current transformers is required to ensure satisfactory operation of measuring instruments and protection relays. Several methods...

Power Factor

Power factor is the ratio between the real power (P in kW) and apparent power (S in kVA) drawn by an electrical load. The reactive power (Q in kVAr)...

Gas Insulated or Air Insulated Switchgear

Various arguments exist around SF6 Gas Insulated (GIS) and Air Insulated (AIS) medium voltage switchgear. Recently we had to change a GIS design to AI...

Michael Faraday (the father of electrical engineering)

Famed English chemist and physicist Michael Faraday was born on September 22, 1791, in Newington Butts, a suburb of Surrey just south of the London Bridge...

How D.C. to A.C. Inverters Work

Traditionally generation of electricity has involved rotating machines to produce alternating sinusoidal voltage and current (a.c. systems). With the development...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note