Earth Electrode Resistance 

By on

Earthing of electrical systems is essential for the correct functioning and the protecting of life and equipment in the event of faults. The earth electrode (connection of the earthing system to the ground) is an essential part of any system.

The estimation of electrode resistance and functioning during the design stage ensures workable solutions are proposed, enhances the operation and potentially reduces the cost of any installation.

General Calculation of Electrode Resistance

Theoretical Example

Sphere of radius r, fully surrounded:

eer1

eer2

eer3

eer4

Method  - assume a current I, is injected into an electrode then at some point distant from the electrode, the current density is:

 myElectrical Equation

If the resistivity of the ground is r, the electric field is:

 myElectrical Equation

By integrating the electric field from the surface of the electrode to infinity, the voltage of the electrode is:

 myElectrical Equation

Apparent resistance Rg, can now be found from:

 myElectrical Equation

Resistance and Distance from an Electrode

ElectrodeResistance
Resistance Contribution v's Distance
Around an earth electrode the resistance of the soil is the sum of series resistances of virtual shells of earth propagating outward from the electrode. Shells nearest to the electrode have the smallest surface area and hence the largest resistance.

The figure illustrates the contribution of the earth to the total resistance of the electrode at increasing distances from the surface of the electrode. As can be seen from the figure, 67% of the total resistance is accounted for at a distance of 0.3 M from the electrode.

In high resistivity locations, decreasing the resistivity in the area close to the electrode by use of ground enhancing materials  (chemical treatment or the use of concrete) will improve the effectiveness of the earth system.

Resistance to Ground (Earth)

The following formula (source: IEEE Std.142:1991) enable the resistance to ground to be calculated.

Hemisphere, radius a myElectrical Equation
One ground rod, length L, radius a myElectrical Equation
Two ground rods, s > L, spacing s myElectrical Equation
Two ground rods, S < L, spacing s myElectrical Equation
Buried horizontal wire, length 2L, depth s/2 myElectrical Equation
Right angle turn of wire, length of arm L, depth s/2 myElectrical Equation
Three point star, length of arm K, depth s/2 myElectrical Equation
Four point star, length of arm L, depth s/2 myElectrical Equation
Six point star, length of arm L, depth s/2 myElectrical Equation
Eight point star, length of arm L, depth s/2 myElectrical Equation
Ring of wire, diameter of ring D, diameter of wire d, depth s/2
myElectrical Equation

Buried horizontal strip, length 2L, section a by b, depth s/2, B < a/8

myElectrical Equation
Buried horizontal round plate, radius a, depth s/2 myElectrical Equation
  Buried vertical round plate, radius a, depth s/2 myElectrical Equation


Where:
   R - resistance in Ω
   ρ - resistivity in Ω.cm
   d - distances - in cm

Multiple Ground Rods

Spacing Factor
No.Rods F
2 1.16
3 1.29
4 1.36
8 1.68
12 1.80
16 1.92
20 2.00
24 2.16




Spaced several rod lengths apart:

myElectrical Equation

Spaced one rod length apart:

myElectrical Equation

 

Ground Enhancing Materials

Ground enhancing materials (GEM) is a technique where the ground immediately surrounding an earth electrode is replaced with a low resistance material. The intent is to reduce the earth electrode resistivity. Use of GEM would be in areas where the ground resistivity is very high and problems arise in trying to achieve the required electrode resistance.

Calculation of Resistance

The resistance, R, expressed in ohms , of a vertical electrode surrounded by an infill of material
is given approximately by the following equation[2]:

myElectrical Equation

Given:
ρ       - resistivity of soil (Ω.m)
ρc     - resistivity of infill material (Ω·m)
d       - diameter of electrode (m)
D       - diameter of infill (m)
L       - length of electrode (m)

Issues and Concerns

GEM treatment may not be permanent and should be check regularly. This is particularly true of chemical treatment which may leach away into the surrounding soil over time resulting in the earth electrode resistance increasing to unacceptable levels. Some GEM treatments may also have corrosive effects on the earth electrode or other negative environmental consequences.

References

  • [1] IEE Std. 142-1991, Grounding of Industrial and Commercial Power Systems, Institute of Electrical and Electronic Engineers
  • [2] BS 7430:1998, Code of Practice for Earthing, British Standards Institute


Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus

  1. Joe 's avatar Joe says:
    7/11/2012 10:13 PM

    How would you approximate resistance if you had a four point star but, two ends of the star had ground rods connected?


Comments are closed for this post:
  • have a question or need help, please use our Questions Section
  • spotted an error or have additional info that you think should be in this post, feel free to Contact Us



Maximum Demand for Buildings

Estimating maximum demand is a topic frequently discussed. Working out how much power to allow for a building can be very subjective . Allowing too much...

Electromechanical Relays

Electromechanical relays have been the traditional backbone of electrical protection systems.  While over recent years these have been replaced by microprocessor...

IEC 61439 Verification Methods

The (relatively new) switchgear and control gear standard, IEC 61439 'Low-voltage switchgear and controlgear assemblies' has three methods which can be...

Robotics - Home Innovations

We have a sister note to this (Robots - Interesting Video), in which I have posted some videos of interesting robots developed by commercial corporations...

Maxwell's Equations - Gauss's Electric Field Law

Gauss's Electrical law defines the relation between charge ("Positive" & "Negative") and electric field.  The law was initially formulated by Carl Friedrich...

Introduction to Current Transformers

Current transformers (CTs) are used to convert high level currents to a smaller more reasonable level for use as inputs to protection relays and metering...

IEC 61439 - The Switchgear Standard

The new standard IEC 61439 replaces the old 60439. Compared to the old standard, the new 61439 is a more clearly defined and takes into account the assembly...

Three Phase Power Simplified

A single phase system is perhaps the most common type of system most people are familiar with. This is what people have in their homes and what appliances...

Welcome back Bottle

‘Kept looking at a card, y’see? Kept looking at it. Welcome back Bottle. Gods below welcome home. The Crippled God A Tale of the Malazan Book of the...

Fire Resistant and Fire Retardant Cables

Fire resistant and fire retardant cable sheaths are design to resist combustion and limit the propagation of flames. Low smokes cables have a sheath designed...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note