Fault Calculation - Symmetrical Components 

By on

Symbol - Definition
image23 - system voltage

image24, image25, image26 - unbalanced voltages
image27, image28, image29 - symmetrical voltages
image21 - circuit impedance

image25 - earth fault impedance

image16 - positive sequence impedance
image17 - negative sequence impedance
image18 - zero sequence impedance

For unbalanced conditions, the calculation of fault currents is more complex. One method of dealing with this is symmetrical components. Using symmetrical components, the unbalanced system is broken down into three separate symmetrical systems:

  • Positive sequence – where the three fields rotate clockwise
  • Negative sequence – where the three fields rotate anti-clockwise
  • Zero sequence – a single field which does not rotate

The positive sequence network rotates clockwise, with a phase of 120° between phases as per any standard a.c. system. 

The negative sequence network rotates anti-clockwise, and the zero sequence network with each phase together (0° apart).

 

Image(29)

Basic Symmetrical Component Theory

Mathematically, the relationship between the symmetrical networks and the actual electrical systems, make use of a rotational operator, denoted by a and given formally by:

Image(27)

Perhaps more simply, the a operator can be looked at as a 120° shift operator. It can also be shown that the following conditions hold true:

Image(28)

By using the a operator, any unbalanced any unbalance three-phase system Va, Vb, Vc can be broken down into three balanced (positive, negative and zero sequence) networks V1, V2, V0.

Unbalanced Network Symmetrical Network
image36   image39
image37  
image38

image41

The operator a, is the unit 120° vector: a = 1|120°. Note: a3=1 and a-1 = a2

Fault Solutions

Once the sequence networks are known, the determination of the magnitude of the fault is relatively straightforward.

The a.c. system is broken down into it's symmetrical components as shown above.  Each symmetrical system is then individually solved and the final solution obtained by superposition of these (as shown above).

For the more common fault conditions,  once the sequence networks are known, we can jump directly to the fault current.  During a fault and letting Un, be the nominal voltage across the branch, the use of symmetrical components gives the following solutions (excluding fault impedance):

Type of Fault Initial Fault Current Comments
three phase image34  
phase to phase image35  
phase to phase image36  
phase to phase to earth image37

image39

image38

Note: the example given assumes a phase to phase fault between L2 and L3 (then shorted to earth)

 

Sequence Impedance Data

Positive, negative and zero sequence impedance data is often available from manufacturers. 

A common assumption is that for non-rotating equipment the negative sequence values are taken to be the same as the positive. 

Zero sequence impedance values are closely tied to the type of earthing arrangements and do vary with equipment type.  While it is always better to use actual data, if it is not available (or at preliminary stages), the following approximations can be used:

Element Z(0)
Transformer  
No neutral connection ∞ (infinity)
Yyn or Zyn 10 to 15 x X(1)
Dyn or YNyn X(1)
Dzn or Yzn 0.1 to 0.2 x X(1)
Rotating Machine
Synchronous 0.5 x Z(1)
Asynchronous zero
Transmission Line 3 x Z(1)

Approximate Zero Sequence Data (source: Schneider)

Related Notes



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus



Write your best report

Years ago I was told that you should always try to write the best report you can.  Many years later I still think on this as one of the better pieces of...

Thomas Edison

American inventor Thomas Alva Edison was born in Milan, Ohio on February 11, 1847. He was the youngest of seven children and received little formal schooling...

Photovoltaic (PV) - Utility Power Grid Interface

Photovoltaic (PV) systems are typically more efficient when connected in parallel with a main power gird. During periods when the PV system generates energy...

Maximum Demand for Buildings

Estimating maximum demand is a topic frequently discussed. Working out how much power to allow for a building can be very subjective . Allowing too much...

Questions - Reputation and Privilege

Our question and answer system while letting you do exactly what it says, is much more.  It is a dynamic user driven system, where our users not only ask...

What is Aircraft Ground Power

Ever wondered what kind of power an aircraft uses when parked at the airport stand. Normally the aircraft generates it own power, but when parked with...

The dc resistance of conductors

This is the first of two posts on the resistance of conductors. In the next post I will look at the ac resistance, including skin effect and we deal with...

Understanding Motor Duty Rating

One of the comments on my Motor Starting Series was asking for something on duty cycles. Here it is. As a purchaser of a motor, you have responsibility...

1,000 kV UHV First for China

At the beginning of the year China put the world's first 1,000 kV UHV transmission system into operation. Transmitting power at over a million volts is...

Always Use PPE

A lot of our members work in countries where PPE (personal protective equipment) is regulated or they work for companies/organizations which take employee...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note