Frame Leakage Protection 

By on

Image
Frame Leakage Protection Principle
While not as popular as it once was, frame leakage protection does still have some use in some circumstances.  In essence frame leakage is an earth fault type protection.  A current transformer installed in a connection from the frame to earth monitors  any fault current and operates an instantaneous relay. 

The fault measuring connection is the only link to earth.  All other connections, including the frame of any switchgear or controlgear assemblies are insulated from earth. 

The main reason for using frame leakage to its ability to detect low levels of fault current.  An example would be a d.c. rail  traction system, where the return rail is insulated (in addition to the switchgear) and by the use of frame leakage protection it is possible to detect high impedance faults away from the switchgear.

In practice it is invariably difficult to fully insulate any item of equipment from earth.  Resistance values of 10 ohms or so would be typical. 

Tip: while insulating the entire switchgear frame,  care must also be taken to use insulating cable glands and in ensuring that no inadvertent earth connections are made.

With the inclusion of transformer neutral earthing, generators, double and sectioned bus bars implementation of frame leakage becomes more complex.  Modern numerical relays are cost effective and provide a large number of features, making them an attractive alternative to the implementation of frame leakage.



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus

  1. naban's avatar naban says:
    4/18/2013 4:16 PM

    If we fix a relay to each of the feeders and one for main switchboard frame if a fault develops in any of the feeders only that feeder will trip,otherwise all feeders won't get supply/power


Comments are closed for this post:
  • have a question or need help, please use our Questions Section
  • spotted an error or have additional info that you think should be in this post, feel free to Contact Us



UPS Sizing - Rules of Thumb

It wasn't so long ago I was telling someone that I don't use rules of thumb as most things are easily calculated anyhow.   As it turns out I last week...

Standard Cable & Wire Sizes

IEC 60228 is the International Electrotechnical Commission's international standard on conductors of insulated cables. Among other things, it defines a...

Robotics - Home Innovations

We have a sister note to this (Robots - Interesting Video), in which I have posted some videos of interesting robots developed by commercial corporations...

Network Theory – Introduction and Review

In electrical engineering, Network Theory is the study of how to solve circuit problems. By analyzing circuits, the engineer looks to determine the various...

Robots - Interesting Videos

The robot folding towels post below was interesting enough at the time to post a link.  Recently I’ve come across a couple of other interesting videos...

The ac resistance of conductors

In a previous article I looked at the dc resistance of conductors and in this article we turn our attention to ac resistance. If you have not read the...

Random Numbers

Using laser optical pulses the random number generator utilizes the time between arrival of random photos to generate the numbers, ensuring true accuracy...

Autonomous Vehicle Challenge

Two driverless and solar power vans have departed from Italy on their way to China via the silk road. During the 13,000 kM trip the vans will drive themselves...

Understanding electric motor insulation & temperature

Anyone specifying or using electric motors should have a basic understanding how the insulation is related to temperature. Three classes of insulation...

How Electrical Circuits Work

If you have no idea how electrical circuits work, or what people mean then they talk about volts and amps, hopefully I can shed a bit light.  I’m intending...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note