How to measure power supply quality 

By on

Fluke430PA
Fluke 430 Power Analyser
If your are ever called out to troubleshoot something on your electrical system, one of the first things consider is the supply voltage.  You want to ensure you have a good electrical supply before moving on to other possible problem causes. Here are a few things you can quickly measure to get an impression on the quality of supply:

  • Measure the supply voltage, current and frequency - you want to make sure all these are within expected limits.  If any of the readings are more than 10% out of range, this indicates a problem.
  • Check for phase unbalance - for three phase loads (i.e. motors), the system should be balanced; voltage unbalance of greater than 2% or current unbalance of greater than 6% would potentially indicate a problem.  You can expect some unbalance for single phase loads the phase, however if this is excessive it may still indicate problems.
  • Check for transients - these are more difficult to measure and will need some sort of recording instrument.  Look for transients 50 V and more above nominal.  You should measure for the duration in line with the observed symptoms.
  • Check for voltage dip - look for dips 50 V and more below nominal. Again measure for the duration in line with the observed symptoms.
  • Check the harmonics on the system - total harmonic distortion (THD) of greater than 6% could indicate problems.
  • Check the power factor - this should be inline with expectations.

The above should provide a fair indication that everything is ok with the supply.  If the supply looks good, you can then start investigating potential problems with the equipment itself.

In special cases, the power system parameters are more strictly defined (i.e. the CBEMA Information Technology Curve).  Where applicable, you should be looking to ensure the supply parameters are within the specification.

If you have any additional tips or suggestions on how to ensure the power supply is up to scratch, feel free to add them below.



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus



IEC 61439 Verification Methods

The (relatively new) switchgear and control gear standard, IEC 61439 'Low-voltage switchgear and controlgear assemblies' has three methods which can be...

Why is electricity so hard to understand?

It's been a busy few months on different projects or busy couple of decades depending on how I look at it. I can say that on the odd (frequent) occasion...

Cost Performance and Time

Often us engineers get so bogged down in equations, using software, producing drawings and writing specifications that this becomes the sole focus.   ...

Introduction to Traction Substations

Following on from my post on railway electrification voltages, I thought an introduction to traction substations would be a good idea. Traction substations...

Tech Topics/Application Notes - Siemens

There are a lot of interesting two page type notes on various medium voltage topics – switchgear, circuit breakers, bus systems etc. It is on the Siemens...

Medium Voltage Switchgear Room Design Guide

Many medium voltage (MV) indoor switchgear rooms  exist worldwide. The complexity of these rooms varies considerably depending on location, function and...

Paths of Flight

GE have put together a time-lapse video shown flight take-off and landings at some airports. An interesting view:

Cable Insulation Properties

Cable insulation is used to provide electrical separation between conductors of  a cable.  During the historical development of cables, numerous types...

Hazardous Areas – IEC and NEC/CEC Comparison

Depending where in the world you work, you are likely following one of two standards International Electrotechnical Commission (IEC) National...

Power Factor

Power factor is the ratio between the real power (P in kW) and apparent power (S in kVA) drawn by an electrical load. The reactive power (Q in kVAr)...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note