Introduction to Current Transformers 

By on

Image(2) 

High Voltage SF6 Current Transformers
Image Source: Courtesy Siemens
Current transformers (CTs) are used to convert high-level currents to a smaller more reasonable level for use as inputs to protection relays and metering equipment.  Within electrical systems, current transformers are essential to ensure the correct functioning and control of equipment and for providing operational data and information.

This introductory note looks at the construction of current transformers and their specification.

There are two broad categories of current transformer:

Measuring CTs -  provide signals to meters and instruments

Protection CTs - provide signals to protective relays to enable correct operation under steady state and transient conditions.

Current transformers work on a similar principal to normal voltage transformers.  Two (or more) winding are wound round a magnetic core.  Current flowing in one winding [the primary] creates a magnetic field which drives current in the other winding [the secondary].  The ratio of the primary turns to the secondary turns provides the current scaling.

Example: a 600:5 ratio CT, for every turn on the primary would have 120 turns on the secondary.  A primary current of 600 A would cause 5 A to flow in the secondary. 

The physical construction of a current transformer can be as simple as one primary winding and one secondary winding on a core.  Quite often the construction is more complex with several secondary windings providing different protection and instrumentation needs. 

Specification of current transformers typically considers the following:

  1. turns ratio - of the primary to secondary current (i.e. 1200/1)
  2. burden - the normal load in VA that the CT can supply
  3. accuracy factors -  the accuracy limits of  (both steady state and transient) 
  4. physical configuration - the number of primary or secondary windings, size, shape, etc.

Safety: if a CT secondary is not connected to any load, then it should be short circuited.  If the secondary of the CT was left open during operation, then you would effectively have a transformer with one turn on the primary and many turns on the secondary.  Large and potentially dangerous voltages would be induced at the secondary terminals. 

Specification of Current Transformers

Current Transformer Accuracy

Accuracy of a current transformer is measured by the composite error.  This is defined as the difference between the ideal secondary RMS current and that of the actual secondary current.  It takes into account current errors, phase error and harmonic errors.

Current transformer intended for protection applications need to cover a wide range of current.  Then current value up to which they will maintain accuracy is the 'accuracy limit current'.   The ratio of the accuracy limit current to the rated current is the 'accuracy limit factor'.

Measuring CT Accuracy Class

Accuracy for measuring current transformers is achieved by allocating an accuracy class to the CT.  For each class, the standards define a maximum allowable current and phase displacement error for different load conditions.

± percentage
current/ratio error
± phase displacement error minutes
Current 5% 20% 50% 100% 120% 5% 20% 100% 120%                                                      
0.1 0.4 0.2   0.1 0.1 15 8 5 5 precision measurements
0.2 0.75 0.35   0.2 0.2 10 15 10 10 precision measurements
0.5 1.5 0.75   0.5 0.5 30 45 30 30 high grade kWhr meters
1 3 1.5   1.0 1.0 60 90 60 60 general measurements
3     3   3         general measurements
5     5   5         approximate measurements

Protection CT Accuracy Class

Protection current transformers are defined as either 5P or 10P.  For each of these the current error, phase displacement error and accuracy limit factor are defined

Class Current
Error
Displacement
Error
Accuracy
Limit Factor
5P ± 1% ± 60 minutes 5
10P ± 3% - 10


Class 'P' current transformers are generally used for overcurrent protection applications.  For more demanding applications, an additional specification is required.  In this instance, the maximum useful emf is often used - specified as the 'knee-point' of the excitation curve ( the point at which a further 10% rise in emf, requires a 50% increase in excitation current).

In addition to the above, other current transformer specifications are also in widespread use:

  • P - general purpose with accuracy defined by composite error and steady-state primary current
  • TPS - low leakage with performance defined by secondary excitation and turns ratio error
  • TPX - defined by peak instantaneous error during specified transient duty
  • TPY - as per TPX, but remanent flux limited to 10%
  • TPZ - breaker failure application CT with large air gap

Name Plate Ratings

Image(3)
Typical Current
Transformer Nameplate
I
mage: Courtesy Schneider Electric
All current transformers should have a nameplate attached.  The image shows an example of a typical nameplate for a current transformer with one primary and two secondary windings (click for a larger version of the image).

Sizing of Current Transformers

The correct sizing and specification of transformers are essential to ensure trouble-free operation of protection and instrumentation systems.  There is a full electrical note dedicated to this at:

How to Size Current Transformers



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus



Arc Flash Calculations

Working in the vicinity of electrical equipment poses an hazard. In addition to electric shock hazard, fault currents passing through air causes Arc Flash...

Closed Doors

"I can live with doubt and uncertainty and not knowing. I think it is much more interesting to live not knowing than to have answers that might be wrong...

Lead Acid Batteries

Lead acid batteries are cost effect and reliable, making them suitable for many applications.This note examines topics of interest associated with the...

Paths of Flight

GE have put together a time-lapse video shown flight take-off and landings at some airports. An interesting view:

Understanding electric motor insulation & temperature

Anyone specifying or using electric motors should have a basic understanding how the insulation is related to temperature. Three classes of insulation...

Tech Topics/Application Notes - Siemens

There are a lot of interesting two page type notes on various medium voltage topics – switchgear, circuit breakers, bus systems etc. It is on the Siemens...

Autonomous Vehicle Challenge

Two driverless and solar power vans have departed from Italy on their way to China via the silk road. During the 13,000 kM trip the vans will drive themselves...

Electric Motors

Collection of links to various places with useful motor information. I’ll try and return to the page every now and again to update it with any motor notes...

Gas Insulated or Air Insulated Switchgear

Various arguments exist around SF6 Gas Insulated (GIS) and Air Insulated (AIS) medium voltage switchgear. Recently we had to change a GIS design to AI...

IEC 61439 - The Switchgear Standard

The new standard IEC 61439 replaces the old 60439. Compared to the old standard, the new 61439 is a more clearly defined and takes into account the assembly...