IEC 61439 Verification Methods 

By on

iec5858The (relatively new) switchgear and control gear standard, IEC 61439 'Low-voltage switchgear and controlgear assemblies' , ensures compliance to the standard by a series of design and routine verifications.

Design Verifications

The standard has three methods which can be used to verify the design characteristics of an assembly will meet the standard. These are verification by test, verification by calculation and verification by the use of design rules.

The following table (table D.1 from Annex D of the standard, IEC:2011) summarizes each characteristic and the allowable options for design verification:

  Verification options
No. Characteristics to be verified Clauses or
subclauses
Testing Calculation Design
Rules
1 Strength of materials and parts:
Resistance to corrosion
Properties of insulating materials:
Thermal stability
Resistance of insulating materials to abnormal
heat and fire due to internal electric effects
Resistance to ultraviolet (UV) radiation
Lifting
Mechanical impact
Marking
10.2
10.2.2
10.2.3
10.2.3.1
10.2.3.2

10.2.4
10.2.5
10.2.6
10.2.7

YES

YES
YES

YES
YES
YES
YES

NO

NO
NO

NO
NO
NO
NO

NO

NO
YES

YES
NO
NO
NO
2 Degree of protection of the enclosures 10.3 YES NO YES
3 Clearances 10.4 YES NO NO
4 Creepage distances 10.4 YES NO NO
5 Protection against electric shock and integrity
of protective circuits:
Effective continuity between the exposed conductive
parts of the assembly and the protective circuit
Short-circuit withstand strength of the protective
circuit
10.5

10.5.2

10.5.3


YES

YES


NO

YES


NO

NO
6 Incorporation of switching devices and components 10.6 NO NO YES
7 Internal electrical circuits and connections 10.7 NO NO YES
8 Terminals for external conductors 10.8 NO NO YES
9 Dielectric properties:
Power-frequency withstand voltage
Impulse withstand voltage
10.9
10.9.2
10.9.3

YES
YES

NO
NO

NO
YES
10 Temperature-rise limits 10.10 YES YES YES
11 Short-circuit withstand strength 10.11 YES YES NO
12 Electromagnetic compatibility (EMC) 10.12 YES NO YES
13 Mechanical operation 10.13 YES NO NO

 

Routine Verification

Routine verification is carried out the detect faults in workmanship and the correct functioning of the panel.  The standard (IEC:2011) list the following:

  1. Construction (see 11.2 to 11.8)
    1. degree of protection of enclosures
    2. clearances and creepage distances
    3. protection against electric shock and integrity of protective circuits
    4. incorporation of built-in components
    5. internal electrical circuits and connections
    6. terminals for external conductors
    7. mechanical operation
  2. Performance (see 11.9 to 11.10)
    1. dielectric properties
    2. wiring, operational performance and function

Original and Assembly Manufacturer

ABBIEC61439Verification
IEC 61439 Verification, Courtesy ABB
The standard also tries to explain the differing roles of the original panel manufacturer and a assembly manufacturer.  The original manufacturer is the party who initially carries out the panel design and arranges for the necessary design verifications to be performed.  The assembly manufacturer is the party who finally builds the panel to the customers requirements and delivers it.    The image shows the relationship between the parties and who performs the verification.

Note: if an assembly manufacturer incorporates his own arrangements, he is then deemed to be the original manufacturer by the standard.

In addition to this post, you may also be interested in my post on 'Forms of Internal Separation' according to the standard:

Switchboard - Forms of Internal Separation



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus

  1. CM3PhaseDesign's avatar CM3PhaseDesign says:
    2/21/2012 12:16 PM

    Hi Steven.
    I just wanted to confirm with you that the table D1 above is now out of date. With the issue of Edition 2 last year this table was amended.

    You can see the current table on our website
    http://www.3phasedesign.com/service.asp?i=48&t=Design%20Verification%20Table

    • Steven's avatar Steven says:
      2/21/2012 1:28 PM

      Thanks for pointing this out. I have updated the table to the 2011 edition.


Comments are closed for this post:
  • have a question or need help, please use our Questions Section
  • spotted an error or have additional info that you think should be in this post, feel free to Contact Us



Railway Electrification Voltages

This post is quick introduction and overview to different railway electrification voltages used in answer to a question sent in via email. While there...

Batteries

A battery consists of one or more cells, each of which use stored chemical energy to produce electrical energy, There are many types of cells and these...

Restricted Earth Fault Protection

The windings of many medium and small sized transformers are protected by restricted earth fault (REF) systems. The illustration shows the principal of...

IEC Document Designation

Often document control is dictated by project requirements, for example a particular organisation may have an existing numbering system. Existing company...

Lead Acid Batteries

Lead acid batteries are cost effect and reliable, making them suitable for many applications.This note examines topics of interest associated with the...

How D.C. to A.C. Inverters Work

Traditionally generation of electricity has involved rotating machines to produce alternating sinusoidal voltage and current (a.c. systems). With the development...

RLC Circuit, Resistor Power Loss - some Modelica experiments

Modelica is an open source (free) software language for modelling complex systems. Having never used it before, I thought I would download a development...

Hazardous Areas – IEC and NEC/CEC Comparison

Depending where in the world you work, you are likely following one of two standards International Electrotechnical Commission (IEC) National...

Operational Amplifier

The fundamental component of any analogue computer is the operational amplifier, or op amp. An operational amplifier (often called an op-amp,) is a high...

Introduction to Lighting

When looking at the design of a lighting scheme it is useful to have an understanding on the nature of light itself and some of the basic theory associated...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note