Periodic Electrical Installation Inspection – How Often? 

By on

periodicInspectionsInspection of electrical installations on a periodic basis is essential to ensure the continued safety and reliability of such installations.

How often installations are inspected is up to the owner of the installation, provided such durations do not exceed any regulatory maximums in force. The criticality of the electrical installation to the continuation of the business, often determines how frequently the installation is inspected, for example many banks will carry out annual inspections of their installations. Other types of enterprise may do inspections more frequently and many installations are only inspected as often as required by regulation.

It is also possible, that different parts of an electrical installation are inspected with varying periods. Critical systems may be inspected more often than non-critical systems.

Depending where you live, it is likely that electrical installation regulations will exist, which will state the maximum duration allowable between inspections. For example in the IEE Wiring Regulations in the UK and the National Electric Code in the US, both deal how long an installation can be left without being inspected.

As an example in the UK, IEE Guidance Note 3, Inspection & Testing contains a table which gives the maximum allowable periods between inspections - offices, residential accommodation five years, leisure complexes, theatres three years, marinas, swimming pools one year, … , etc.

Now that the when has been covered, my second post will look at what should be inspected:

Periodic Electrical Installation Inspection – What to Inspect?



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus

  1. Eurotechworld's avatar Eurotechworld says:
    6/7/2012 7:11 PM

    It is wonderful information and very helpful in business. Thanks for shearing this topic friend.

    Third Party Inspection


Comments are closed for this post:
  • have a question or need help, please use our Questions Section
  • spotted an error or have additional info that you think should be in this post, feel free to Contact Us



Paths of Flight

GE have put together a time-lapse video shown flight take-off and landings at some airports. An interesting view:

Photovoltaic (PV) Panel - Performance Modelling

In an earlier note on the site [Photovoltaic (PV) - Electrical Calculations], the theory of solar (PV) cell calculations was introduced.  In particular...

IEC 61439 Verification Methods

The (relatively new) switchgear and control gear standard, IEC 61439 'Low-voltage switchgear and controlgear assemblies' has three methods which can be...

Smarter Electrical Distribution

The other day I came across an article in Technology Review on the development of a smart transformer. A professor at North Carolina State University is...

Tips for a better Low Voltage Protection Discrimination Study

Carrying out a protection system discrimination study is critical to ensure the correct functioning of  the electrical system in the event of faults. ...

Restricted Earth Fault Protection

The windings of many medium and small sized transformers are protected by restricted earth fault (REF) systems. The illustration shows the principal of...

Motor Insulation

Insulation on a motor prevents interconnection of windings and the winding to earth.  When looking at motors, it is important to understand how the insulation...

Dielectric loss in cables

Dielectrics (insulating materials for example) when subjected to a varying electric field, will have some energy loss.   The varying electric field causes...

Battery Cars A to Z

Battery powered cars are a hot topic and widely debated. The pros, cons, issues and time frames can be talked about endlessly. An article by the Telegraph...

UPS Sizing - Rules of Thumb

It wasn't so long ago I was telling someone that I don't use rules of thumb as most things are easily calculated anyhow.   As it turns out I last week...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note