Cable Sheath and Armour Loss 

By on

When sizing cables, the heat generated  by losses within any sheath or armour need to be evaluated. When significant, it becomes a factor to be considered in the sizing of cables.  To understand how sheath and armour losses affect the sizing of cables, you can review the post: IEC 60287 Current Capacity of Cables - Rated Current

This note looks at how to obtain the necessary loss factors for use within the IEC 60287 calculation.  In addition, the loss factors quantify the ratio of losses in the sheath to total losses in all conductors and have application outside the IEC 60287 standard.

Calculation of Sheath and Armour Loss

Any cable sheath (or screen) the loss λ1, consists of two components:

  λ 1 = λ 1 + λ 1

  • λ1' - losses caused by circulating currents.  These losses only occur in single core cables and for any circulating current to be present, it is necessary to the sheaths of each cable to be bonded at two or more points along its length.
  • λ1''  - losses caused by eddy currents.  These are small circulating currents setup in the sheath due to changing magnetic fields.

The loss in armour is considered as only one component, λ2.

Sheath and armour losses are only applicable to alternating current (a.c.) cables.  The actual formula for calculation of sheath and armour loss depend on the installation and arrangement of cables.  The tables below presents some of the common installation situations and are based on equations given in IEC 60287:

Calculation of sheath or screen loss in - Single Core Cables

For installations bonded only at one point, circulating currents are not possible and the loss is zero. Except in the case of large segmental type conductors (see Some Special Cases below), eddy current loss λ1'', for single core cables can be ignored.

     Sheath Circulating Current Loss, λ1' 
Single core cables
- trefoil, bonded at both ends  

  λ 1 = R S R 1 1+ ( R s X ) 2

Single core cables
- flat, with transposition, bonded at both ends

  λ 1 = R S R 1 1+ ( R s X ) 2

Single core cables
- flat, without transposition, bonded at both ends

λ11 - loss factor for the outer cable with the greater losses
     λ 11 = R s R [ 0.75 P 2 R s 2 + P 2 + 0.25 Q 2 R s 2 + Q 2 + 2 R s PQ X m 3 ( R s 2 + P 2 )( R s 2 + P 2 ) ]

λ12 - loss factor for the outer cable with the least losses
  λ 12 = R s R [ 0.75 P 2 R s 2 + P 2 + 0.25 Q 2 R s 2 + Q 2 2 R s PQ X m 3 ( R s 2 + P 2 )( R s 2 + P 2 ) ]

λ1m - loss factor for the middle cable
  λ 1m = R s R Q 2 R s 2 + Q 2

where: 
  P=X+ X m
  Q=X+ X m 3

 

Calculation of sheath or screen loss in - Multi-Core Cables

Due to any sheath or screen surrounding all cores, the possibility of circulating current does not exist, and the λ1' loss can be ignored.  Eddy current loss, λ1'' does need to be considered.

    Sheath Eddy Current Loss, λ1'' 
Two core cable - common sheath, unarmoured    - for round or oval conductors
  λ 1 = 16 ω 2 10 14 R R s ( c d )[ 1+ ( c d ) 2 ]

- for sector shaped conductors
  λ 1 = 10.8 ω 2 10 16 R R s ( 1.48 r 1 +t d )[ 12.2+ ( 1.48 r 1 +t d ) 2 ]
Three core cable - common sheath, unarmoured

- round or oval conductors, Rs ≤ 100 µΩ.m-1
  λ 1 = 3 R s R [ ( 2c d ) 2 1 1+ ( R s ω 10 7 ) 2 + ( 2c d ) 4 1 1+4 ( R s ω 10 7 ) 2 ]



- round or oval conductors, Rs >100 µΩ.m-1
  λ 1 = 3.2 ω 2 R R s ( 2c d ) 2 10 14

- for sector shaped conductors (any Rs)
  λ 1 =0.94 R s R ( 2 r 1 +t d ) 2 1 1+ ( R s ω 10 7 ) 2

Two or three core cable - steel tape armour

Multiple the unarmoured cable factor by:
  [ 1+ ( d d A ) 2 1 1+ d A μδ ] 2

Cables with each core in a separate sheath or pipe type cables
  λ 1 = R s R 1.5 1+( R s X SL )

where:
  X SL =2ω 10 7 ln( 2c d )

 

Calculation of armour loss

For armoured cables, the losses are estimated as shown.

   Armour Loss, λ2  
Non-magnetic armour  Use equation for λ1'', substituting:
  • parallel combination of sheath and armour resistance for Rs
  • root mean square of sheath and armour diameter for d
Single core cables - steel wire armour
General advice is not to use magnetic armour for single core cables. 
If required, then the guidelines given in IEC 60287 on estimating losses should be followed. 
Two core cable - steel wire armour

  λ 2 = 0.62 ω 2 10 14 R R A + 3.82 A ω 10 5 R [ 1.48 r 1 +t d A 2 +95.7A ] 2

Three core cable - steel wire armour - round conductor 
  λ 2 =1.23 R A R ( 2c d A ) 2 1 ( 2.77 R A 10 6 ω ) 2 +1

- sector shaped conductor
  λ 2 =0.358 R A R ( 2 r 1 d A ) 2 1 ( 2.77 R A 10 6 ω ) 2 +1

 

Calculating the Parameters

Sheath (Rs) or armour (RA) resistance  - values used above are calculated at their operating temperature.  The operating temperature (in °C) and resistance can be determined from:

  θ sc =θ( I 2 R+0.5 W d )× T 1    - for any sheath

  θ ar =θ{ ( I 2 R+0.5 W d )× T 1 +[ I 2 R( 1+ λ 1 )+ W d ]×n T 2 }     - for any armour

  R s = R s20 [ 1+ α 20 ( θ sc 20 ) ]    - for the cable sheath

  R A = R A20 [ 1+ α 20 ( θ ar 20 ) ]    - for the cable armour

 

Note: for calculation of the dielectric loss Wd, refer to our Dielectric loss in cables note.

Cable Reactance - for single core cables, where there is significant spacing between conductors, it is necessary to use the reactance in the calculating of circulating current loss.  Accurate values for reactance can be obtained from cable manufacturers or by using software.  Alternatively, the following equations can be used to estimate the reactance (Ω.m-1):

Single core cable reactance estimates (assume bonded at both ends)

  X=2ω 10 7 ln( 2s d )    - trefoil or flat without transposition

  X=2ω 10 7 ln( 2 3 2 s d )   - flat with transposition

   X m =2ω 10 7 ln( 2 ) -  mutual reactance of flat formation cables

Steel tape armour resistance - depending on how steel tape is wound, the resistance can be estimated as follows:
  1. tapes laid longitudinally - calculate the resistance as that of an equivalent cylinder (same mass and diameter)
  2. tapes laid ≈54° to cable axis - use twice the value obtained from (1)
  3. tapes with a very short lay - take resistance as infinite (neglect losses)
  4. tapes with a very short lay (double layered) - use twice the value obtained form (1)

Cable Transposition

Transposing of cables (see image) is a technique to reduce the circulating currents within cable sheaths and consequently increase the rating of the cable.

 

Cable Cross Bonding
Transposed and cross bonded cable

By cross bonding the sheath the induced currents are in opposite directions, cancelling each other out and significantly improving the current rating of the cable.  Transposing the cables ensures that the reactance balance out and aids in implementation.

At intermediate transposition points, over voltage devices are installed to protect the cable and personnel in the event of voltage build up during faults.

In practice, three minor sections (part between the cross bond) would from a major section (three full transpositions).  It makes sense to do these at each joint point - at each cable drum length.

Transposition and cross bonding are normally carried out in link boxes.

Some Special Situations

Large segmental type conductors

Eddy current losses λ1'', are normally small relative to other losses and can be ignored for single core cables.  This changes for large conductors, which are of a segmented construction.  Under these conditions, the eddy current loss should be considered.

For this condition, the value of λ1'' is derived from the circulating current loss factor λ1' by:

  λ 1 = λ 1 × 4 M 2 N 2 + ( M+N ) 2 4( M 2 +1 )( N 2 +1 )

where:

  M=N= R s X    - for cables in trefoil

  M= R s X+ X n    and   N= R s X X m 3    - for cable in flat formation

Single core cables - variation of route spacing

If the spacing if not maintained the same for the full cable route than the reactance will vary along the route.  In instances such as these, an equivalent overall reactance can be calculated from:

  X= l a X a + l b X b ++ l n X n l a + l b ++ l n

- where la, lb, ... are the section lengths and Xa, Xb, ... are the reactance of each section

Symbols

A - armour cross sectional area, mm2
R - conductor a.c. resistance, Ω.m-1
RA - armour resistance maximum at operating temperature, Ω.m-1
RA20 - armour resistance at 20 °C, Ω.m-1
Rs - sheath or screen resistance at maximum operating temperature,  Ω.m-1
Rs20 - sheath or screen resistance at 20 °C, Ω.m-1
X - sheath or screen reactance, Ω.m-1
Xm - mutual reactance (sheath one cable to conductors of other cables), Ω.m-1


 λ1 - ratio of sheath loss to total conductor loss 
λ2 - ratio of armour loss to total conductor loss

λ1'  - sheath loss caused by circulating currents
λ1''  - sheath loss caused by eddy currents
c  - distance between axis of conductors, mm
d - mean diameter of sheath or screen, mm
dA - mean diameter of armour, mm
r1 - circumscribing radius of sector shaped conductors, mm
s - axial separation of conductors, mm
t - insulation thickness between conductors, mm
T1 - thermal resistance between conductor and sheath, K.m.W-1
T2 - thermal resistance between sheath and armour, K.m.W-1


θ  - maximum conductor temperature, °C
θar - maximum operating temperature of armour, °C
θsc - maximum operating temperature of screen, °C
ω - angular frequency (2πf)
µ - relative magnetic permeability of armour
δ - equivalent thickness of armour, mm

See Also



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus



Photovoltaic (PV) Panel - Performance Modelling

In an earlier note on the site [Photovoltaic (PV) - Electrical Calculations], the theory of solar (PV) cell calculations was introduced.  In particular...

Thomas Edison

American inventor Thomas Alva Edison was born in Milan, Ohio on February 11, 1847. He was the youngest of seven children and received little formal schooling...

Post Authorship

In 2011, with the introduction of it’s Panda search ranking algorithms, Google introduced tools for determining the original author of posts.  The intention...

Understanding electric motor insulation & temperature

Anyone specifying or using electric motors should have a basic understanding how the insulation is related to temperature. Three classes of insulation...

How to Check a Circuit is Dead

If you want to check a circuit is dead (not live), you should always use the three point method. First check a known live circuit, then check the dead...

What is Aircraft Ground Power

Ever wondered what kind of power an aircraft uses when parked at the airport stand. Normally the aircraft generates it own power, but when parked with...

What is an Open Delta Transformer

In three phase systems, the use of transformers with three windings (or legs) per side is common.  These three windings are often connected in delta or...

The ac resistance of conductors

In a previous article I looked at the dc resistance of conductors and in this article we turn our attention to ac resistance. If you have not read the...

MIT OpenCourseWare

MIT OpenCourseWare, makes the materials used in teaching all MIT subjects available on the Web, free of charge, to any user in the world.

Induction Motor Calculator

Just added a page to the tools, which will allow you to calculate the synchronous speed, slip and rated torque for an induction motor. Not a particularly...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note