IEC 61439 - The Switchgear Standard 

By on

Switchboard_Front
IEC 61439 -
The New Switchgear Standard
The new standard IEC 61439 replaces the old 60439.  Compared to the old standard, the new 61439 is a more clearly defined and takes into account the assembly of pre-tested designs. . 

Some key differences are that the distinction between type tested assemblies (TTA) and partially type tested (PTTA) is gone, verifying the performance is addressed in new ways and the specification of current ratings is updated.  

For more information on testing to the standard, see:

IEC 61439 Verification Methods

Current Ratings

Within the 61439, current ratings are clarified and more clearly defined.t ratings.

  • The standard defines the overall rated current of the assembly (Ina) as the smaller of the sum of  rated currents of incoming circuits or the total current the main busbar is capable of distributing.
  • The rated current of a circuit (Inc) is the rating of a circuit taking in to account the installed devices, disposition and application (and may be lower than the rated current of the devices used).
  • A rated diversity factor (RDF) is assigned by the manufacturer to groups of outgoing circuits which can be simultaneously loaded and takes into account the mutual thermal influence between the circuits.  This can be applied to the whole assembly or a group of circuits.

This clarification of ratings ties the consideration and specification of a switchboard more closely into the manufactured product.  Personally I think is a good thing.  It does put more emphasis on specifiers to understand how the assembly will perform and what they want out of it. 

Typical RDF

The RDF is a figure to be given by manufacturers.  Some typical values I found on the Schneider website are:

Number of main outgoing circuits

Diversity factor

2 and 3

0.9

4 and 5

0.8

6 to 9 inclusive

0.7

10 and more

0.6

 

Specification of Switchboards

The standard will change how specifiers state their requirements.  Currently specification is often carried out based around devices (i.e. circuit breakers from a particular manufacturer for example), with the device ratings being applied to switchboards.  This is not the case any longer.  There is now a clear need to consider the effect of the enclosure and surrounding components in addition to those of the protective devices and trip units. 

See Also



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus



Occam's Razor

I was reminded of Occam's Razor while reading a book. It's quite a simple principal of logic which has stood the test of time and is accepted as central...

A mechanical engineering paper, some history and memories

I was digging in my bookshelf and came across the 80th Anniversary Association of Mine Resident Engineers, Papers and Discussions Commemorative Edition...

Useful Motor Technical Information

Sometimes it’s useful to be able to quickly lookup a piece of technical information.  This note is a collection of information related to motors, and in...

Restricted Earth Fault Protection

The windings of many medium and small sized transformers are protected by restricted earth fault (REF) systems. The illustration shows the principal of...

Material Properties

Everything physical in electrical engineering from insulations to conductors revolves around materials. Here we are listing common materials along with...

Tips for a better Low Voltage Protection Discrimination Study

Carrying out a protection system discrimination study is critical to ensure the correct functioning of  the electrical system in the event of faults. ...

Getting Started with Patents

If you have a great idea or invent something the last thing you want is someone to steal the idea. One of the things you can do is protect the intellectual...

What is an Open Delta Transformer

In three phase systems, the use of transformers with three windings (or legs) per side is common.  These three windings are often connected in delta or...

Back to basics - the Watt (or kW)

When thinking about watts (W) or kilowatt (kW = 1000 W) it can be useful too keep in mind the fundamental ideas behind the unit. Watt is not a pure electrical...

Understanding Circuit Breaker Markings

IEC 60947 is the circuit breaker standard and covers the marking of breakers in detail. Any manufacturer following this standard should comply with the...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note