Low Voltage Fault Tables 

By on

The following tables provide quick order of magnitude fault levels for a a range of typical low voltage situations.

Transformer LV Terminal Fault Levels (230/400 V)

Short circuit current, Isc (kA) at the LV terminals of a 3-phase HV/LV transformer.

Transformer rated power (kVA) 50 100 160 250 315 400 500 630 800 1000 1250 1600 2000 2500
Transformer rated (LV) current (A) 69 137 220 344 433 550 687 866 1100 1375 1718 2199 2749 3437
oil-immersed Psc = 250MVA 1.17 33.1 3.40 5.41 8.38 10.5 13.2 16.4 17.4 20.4 21.5 26.4 40.4 49.1
  Psc = 500 MVA 1.17 3.42 5.45 8.49 10.7 13.5 16.8 21.0 17.9 22.2 27.5 34.8 43.0 52.9
cast-resin Psc = 250 MVA 1.14 2.28 3.63 5.63 7.07 8.93 11.1 13.9 17.4 21.5 26.4 33.1 40.4 49.1
  Psc = 500 MVA 1.14 2.28 3.65 5.68 7.14 9.04 11.3 14.1 17.9 22.2 27.5 34.8 43.0 52.9

Psc - Short circuit current at HV windings

Short Circuit Current of Feeders

Short circuit current, Isc at receiving end of a feeder in terms of the short circuit at it's sending end.

Copper 230/400 V

Example of using the table - 10 mm2 cable, 6.5 m in length, upstream fault 35 kA, gives downstream fault of 11 kA

csa (mm²) length of circuit (m)
1.5                           0.8 1 1.3 1.6 3
2.5                         1 1.3 1.6 2.1 2.6 5
4                       0.8 1.7 2.1 2.5 3.5 4 8.5
6                       1.3 2.5 3 4 5 6.5 13
10                   0.8 1.1 2.1 4 5.5 6.5 8.5 11 21
16               0.9 1 1.4 1.7 3.5 7 8.5 10 14 17 34
25             1 1.3 1.6 2.1 2.6 5 10 13 16 21 26 50
35             1.5 1.9 2.2 3 2.5 7.5 15 19 22 30 37 75
50           1.1 2.1 2.7 3 4 5.5 11 21 27 32 40 55 110
70           1.5 3 3.5 4.5 6 7.5 15 30 37 44 60 75 150
95       0.9 1 2 4 5 6 8 10 20 40 50 60 80 100 200
120   0.9 1 1.1 1.3 2.5 5 6.5 7.5 10 13 25 50 65 75 100 130 250
150 0.8 1 1.1 1.2 1.4 2.7 5.5 7 8 11 14 27 55 70 80 110 140 270
185 1 1.1 1.3 1.5 1.6 3 6.5 8 9.5 13 16 32 65 80 95 130 160 320
240 1.2 1.4 1.6 1.8 2 4 8 10 12 16 20 40 80 100 120 160 200 400
300 1.5 1.7 1.9 2.2 2.4 5 9.5 12 15 19 24 49 95 120 150 190 240  
2 x 120 1.5 1.8 2 2.3 2.5 5.1 10 13 15 20 25 50 100 130 150 200 250  
2 x 150 1.7 1.9 2.2 2.5 2.8 5.5 11 14 17 22 28 55 110 140 170 220 280  
2 x 185 2 2.3 2.6 2.9 3.5 6.5 13 16 20 26 33 65 130 160 200 260 300  
3 x 120 2.3 2.7 3 3.5 4 7.5 15 19 23 30 38 75 150 190 230 300 380  
3 x 150 2.5 2.9 3.5 3.5 4 8 16 21 25 33 41 80 160 210 250 330 410  
3 x 185 2.9 3.5 4 4.5 5 9.5 20 24 29 39 49 95 190 240 290 300    
Isc (kA) upstream Isc (kA) downstream
100 94 94 93 92 91 83 71 67 63 56 50 33 20 17 14 11 9 5
90 85 85 84 83 83 76 66 62 58 52 47 32 20 16 14 11 9 4.5
80 76 76 75 75 74 69 61 57 54 49 44 31 19 16 14 11 9 4.5
70 67 67 66 66 64 61 55 52 49 45 41 29 18 16 14 11 5 4.5
60 58 58 57 57 57 54 48 46 44 41 38 27 18 15 13 10 8.5 4.5
50 49 48 48 48 48 46 42 40 39 36 33 25 17 14 13 10 8.5 4.5
40 39 39 39 39 39 37 35 33 32 30 29 22 15 13 12 9.5 8 4.5
35 34 34 34 34 34 33 31 30 29 27 26 21 15 13 11 9 8 4.5
30 30 29 29 29 29 28 27 26 25 24 23 19 14 12 11 9 7.5 4.5
25 25 25 25 24 24 24 23 22 22 21 20 17 13 11 10 8.5 7 4
20 20 20 20 20 20 19 19 18 18 17 17 14 11 10 9 7.5 6.5 4
15 15 15 15 15 15 15 14 14 14 13 13 13 9.5 8.5 8 7 6 4
10 10 10 10 10 10 10 9.5 9.5 9.5 9.5 9 8.5 7 6.5 6.5 5.5 5 3.5
7 7 7 7 7 7 7 7 7 6.5 6.5 6.5 6 5.5 5 5 4.5 4 2.9
5 5 5 5 5 5 5 5 5 5 5 5 4.5 4 4 4 3.5 3.5 2.5
4 4 4 4 4 4 4 4 4 4 4 4 3.5 3.5 3.5 3 3 2.9 2.2
3 3 3 3 3 3 3 3 3 2.9 2.9 2.9 2.8 2.7 2.6 2.5 2.4 2.3 1.9
2 2 2 2 2 2 2 2 2 2 2 2 1.9 1.9 1.8 1.8 1.7 1.7 1.4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.9 0.9 0.9 0.8

Note: for a 3-phase system having 230 V between phases, divide above lengths by 1.732

Aluminium 230/400 V

csa (mm²) length of circuit (m)
2.5                           0.8 1 1.3 1.6 3
4                         1 1.3 1.6 2.1 2.6 5
6                       0.8 1.6 2 2.4 3 8 8
10                       1.3 2.6 3.5 4 5.5 6.5 13
16                   0.8 1.1 2.1 4 5.5 6.5 8.5 11 21
25               0.8 1 1.3 1.7 3.5 6.5 8.5 10 13 17 33
35             0.9 1.2 1.4 1.8 2.3 4.5 9 12 14 18 23 46
50             1.3 1.7 2 2.6 3.5 6.5 13 17 20 26 33 65
70           0.9 1.8 2.3 2.8 3.5 4.5 9 18 23 28 37 46 90
95           1.3 2.5 3 4 5 6.5 13 25 32 38 50 65 130
120         0.8 1.7 3 4 4.5 6.5 8 17 32 40 47 65 80 160
150         0.9 1.7 3.5 4.5 5 7 8.5 17 34 43 50 70 85 170
185       0.9 1 2 4 5 6 8 10 20 40 50 60 80 100 240
240   0.9 1 1.1 1.3 2.5 5 6.5 7.5 10 13 25 50 65 75 100 130 250
300 0.9 1 1.2 1.4 1.5 3 6 7.5 9 12 15 30 60 75 90 120 150 300
2 x 120 0.9 1.1 1.3 1.4 1.6 3 6.5 8 9.5 13 16 32 65 80 95 130 160 320
2 x 150 1 1.2 1.4 1.5 1.7 3.5 7 9 10 14 17 35 70 85 100 140 140  
2 x 185 1.2 1.4 1.6 1.8 2 4.1 8 10 12 16 20 41 80 100 120 160 200  
2 x 240 1.5 1.8 2 2.3 2.5 5 10 13 15 20 25 50 100 130 150 200 250  
3 x 120 1.4 1.7 1.9 2.1 2.4 4.5 9.5 12 14 19 24 48 95 120 140 190 240  
3 x 150 1.5 1.8 2.1 2.3 2.6 5 10 13 15 21 26 50 100 130 150 210 260  
3 x 185 1.8 2.1 2.4 2.7 3 6 12 15 18 24 30 60 120 150 180 240 300  
3 x 240 2.3 2.7 3 3.5 4 7.5 15 19 23 30 38 75 150 190 230 300 380  
Isc (kA) upstream Isc (kA) downstream
100 94 94 93 92 91 83 71 67 63 56 50 33 20 17 14 11 9 5
90 85 85 84 83 83 76 66 62 58 52 47 32 20 16 14 11 9 4.5
80 76 76 75 75 74 69 61 57 54 49 44 31 19 16 14 11 9 4.5
70 67 67 66 66 64 61 55 52 49 45 41 29 18 16 14 11 5 4.5
60 58 58 57 57 57 54 48 46 44 41 38 27 18 15 13 10 8.5 4.5
50 49 48 48 48 48 46 42 40 39 36 33 25 17 14 13 10 8.5 4.5
40 39 39 39 39 39 37 35 33 32 30 29 22 15 13 12 9.5 8 4.5
35 34 34 34 34 34 33 31 30 29 27 26 21 15 13 11 9 8 4.5
30 30 29 29 29 29 28 27 26 25 24 23 19 14 12 11 9 7.5 4.5
25 25 25 25 24 24 24 23 22 22 21 20 17 13 11 10 8.5 7 4
20 20 20 20 20 20 19 19 18 18 17 17 14 11 10 9 7.5 6.5 4
15 15 15 15 15 15 15 14 14 14 13 13 13 9.5 8.5 8 7 6 4
10 10 10 10 10 10 10 9.5 9.5 9.5 9.5 9 8.5 7 6.5 6.5 5.5 5 3.5
7 7 7 7 7 7 7 7 7 6.5 6.5 6.5 6 5.5 5 5 4.5 4 2.9
5 5 5 5 5 5 5 5 5 5 5 5 4.5 4 4 4 3.5 3.5 2.5
4 4 4 4 4 4 4 4 4 4 4 4 3.5 3.5 3.5 3 3 2.9 2.2
3 3 3 3 3 3 3 3 3 2.9 2.9 2.9 2.8 2.7 2.6 2.5 2.4 2.3 1.9
2 2 2 2 2 2 2 2 2 2 2 2 1.9 1.9 1.8 1.8 1.7 1.7 1.4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0.9 0.9 0.9 0.8

Note: for a 3-phase system having 230 V between phases, divide above lengths by 1.732



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus

  1. Sinnadurai's avatar Sinnadurai says:
    7/11/2012 11:59 AM

    Give a method of calculating/evaluating fault current contributed by motors(induction/synchrounous)

    • Steven's avatar Steven says:
      7/11/2012 12:44 PM

      IEC 60909 gives some guidelines on how to take into account motor contribution. You can also refer to the following (which gives a guideline on if it is necessary to consider motors):

      http://myelectrical.com/notes/entryid/192/fault-calculations-introduction

      At some stage in the future, I’ll put a post together on this (noted in the my list of future posts).


Comments are closed for this post:
  • have a question or need help, please use our Questions Section
  • spotted an error or have additional info that you think should be in this post, feel free to Contact Us



New Mail Chimp

We've been sending out Newsletters on a regular basis for a few weeks now. To do this we have been using Google's Feedburner service. While Feedburner...

Aluminium Windings - Dry Type Transformers

The other day I was talking to a colleague who is a building services consultant.  Despite regularly specifying dry-type/cast resin transformers he was...

Harmonised Cable Codes and Colours

Within Europe the European Committee for Electrotechnical Standardization (CENELEC) has standardised the both the designation and colour of cables.   ...

How to Write an Electrical Note

Electrical notes are a collaborative collection of electrical engineering information and educational material. Any registered user can add content. ...

Cable Insulation Properties

Cable insulation is used to provide electrical separation between conductors of  a cable.  During the historical development of cables, numerous types...

Power Factor

Power factor is the ratio between the real power (P in kW) and apparent power (S in kVA) drawn by an electrical load. The reactive power (Q in kVAr)...

Lead Acid Batteries

Lead acid batteries are cost effect and reliable, making them suitable for many applications.This note examines topics of interest associated with the...

Introduction to Traction Substations

Following on from my post on railway electrification voltages, I thought an introduction to traction substations would be a good idea. Traction substations...

Photovoltaic (PV) Panel - Performance Modelling

In an earlier note on the site [Photovoltaic (PV) - Electrical Calculations], the theory of solar (PV) cell calculations was introduced.  In particular...

Introduction to Current Transformers

Current transformers (CTs) are used to convert high level currents to a smaller more reasonable level for use as inputs to protection relays and metering...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note