Motor Insulation 

By on

Insulation on a motor prevents interconnection of windings and the winding to earth. When looking at motors, it is important to understand how the insulation functions and its practical application.

Rating

motorInsulationClass
Motor Insulation Class

IEC 60085 ‘Electrical insulation - Thermal evaluation and designation ’ divides insulation into classes. Each class is given a designation that corresponds to the upper temperature limit of the insulating material when used under normal operating conditions.

The correct insulation of the winding of a motor is determined by both the temperature rise in the motor and the temperature of the ambient air.

If a motor is subjected to an ambient temperature higher than 40o C, it must normally be de-rated or a higher insulation class of material used.

Note: motors are typically rated for class 'B' or 'F' insulation

Tip: specify a class ‘F’ insulation, but a class ‘B’ temperature rise.  This gives a 25o C margin – can be used for high ambient temperatures for example.

IEC – NEMA Temperature Rise

The table below compares the IEC temperature rise ratings, with the NEMA specification:

Insulation
Class 
  IEC   NEMA
[1.0 SF]
NEMA
[1.5 SF] 

A

60

60

70

E

75

-

-

B

80

80

90

F

100

105

115

H

125

125

-

* SF - NEMA Service Factor

Insulation Life and Temperature

If the upper temperature limit of the insulation material is exceeded the life of the insulation will be reduced at illustrated below.

The selection of insulation class is critical to the life of the motor.  A common rule of thumb is that the life of the motor insulation will be halved for every 8 to 10 °C it is operated above the rated insulation temperature

motorInsulationLifeTime
Motor Life and Temperature

Testing Insulation

Prior to putting the motor into operations, during routine maintenance and fault finding an insulation tester is used to measure the motor insulation and verify it’s suitability.

Insulation Test Voltages

Motor Voltage (V) DC Test Voltage (V)
< 2000 500
2001 - 4000 1000 *
4001 - 8000 2500 *
8001 - 16000 5000 *

Check Resistance First Using 500 V 

Recommended Winding Resistance Values

Given a line to line voltage V (kV), winding temperature T (oC) then the minimum insulation resistance (MΩ) of the complete winding should be greater than: 

{R_w} - \left( {V + 1} \right){e^{k - 0.692\,T}}

k = 4.159 for a new machine, clean, dry
k = 2.869 for aged machine, clean, uncontaminated
k = 2.771 machine after several years, normal industrial pollution

On a three phase winding the resistance of each phase:

{R_{ph}} = 2{R_w}

Polarisation Index

motorDryingOutProcess
Motor Drying Out Process

The polarisation index is the ratio of the winding insulation resistance measured after applying the test voltage for 10 minutes to the value obtained after 1 minute and is used as a guide to the dryness of the winding.

{\rm{Polarisation Index }} = \frac{{{R_{10}}}}{{{R_`}}}

A clean dry winding will typically give a value greater than 1.5. The lower the ratio the greater the leakage path to ground (in effect the capability of the insulation to hold a capacitive charge).

No exact cut-off values exist (1.25 to 2.5 being common). The best guide is a constant ratio over successive readings taken periodically



Steven McFadyen's avatar Steven McFadyen

Steven has over twenty five years experience working on some of the largest construction projects. He has a deep technical understanding of electrical engineering and is keen to share this knowledge. About the author

myElectrical Engineering

comments powered by Disqus



Bows and Arrows

It starts with me reading one of the Horrible History books with my son (Groovy Greeks). Arrows were mentioned which lead to the discussion of the bodkin...

What is an Open Delta Transformer

In three phase systems, the use of transformers with three windings (or legs) per side is common.  These three windings are often connected in delta or...

Wiki Depreciation

We have had the Wiki with us for a long time now, but at last I have decided to say bye bye – more details on why below.

How to Size Current Transformers

The correct sizing of current transformers is required to ensure satisfactory operation of measuring instruments and protection relays. Several methods...

IEC 61439 Verification Methods

The (relatively new) switchgear and control gear standard, IEC 61439 'Low-voltage switchgear and controlgear assemblies' has three methods which can be...

Questions - Reputation and Privilege

Our question and answer system while letting you do exactly what it says, is much more.  It is a dynamic user driven system, where our users not only ask...

Maxwell's Equations - Gauss's Electric Field Law

Gauss's Electrical law defines the relation between charge ("Positive" & "Negative") and electric field.  The law was initially formulated by Carl Friedrich...

IEC 61439 - The Switchgear Standard

The new standard IEC 61439 replaces the old 60439. Compared to the old standard, the new 61439 is a more clearly defined and takes into account the assembly...

Fault Calculations - Typical Equipment Parameters

A frequent problem in fault calculations is the obtaining of equipment parameters.  While it is always preferable to use the actual parameters of the equipment...

IEC Reference Designations

The IEC publishes a series of documents and rules governing the preparation of documents, drawings and the referencing of equipment.   Depending on country...

Have some knowledge to share

If you have some expert knowledge or experience, why not consider sharing this with our community.  

By writing an electrical note, you will be educating our users and at the same time promoting your expertise within the engineering community.

To get started and understand our policy, you can read our How to Write an Electrical Note.